Signals; Settings - ABB RELION 630 Series Technical Manual

Power management
Hide thumbs Also See for RELION 630 Series:
Table of Contents

Advertisement

1MRS757256 F
3.27.4
3.27.5
Table 105:
GOOSESPRCV Non group settings (basic)
Name
Values (Range)
Operation
PML630/Compact Load-Shedding Solution
Technical Manual
The input of this GOOSE block must be linked in Signal Matrix by
means of a cross to receive the binary single point values.
The implementation for IEC 61850 quality data handling is restricted
to a simple level. If quality data validity is GOOD, the DATAVALID
output is HIGH. If quality data validity is INVALID,
QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA, the
DATAVALID output is LOW.

Signals

Table 103:
GOOSESPRCV Input signals
Name
BLOCK
Table 104:
GOOSESPRCV Output signals
Name
SPOUT
DATAVALID
COMMVALID
TEST

Settings

Unit
Off
-
On
Type
Default
Description
BOOLEAN
0
Block of function
Type
Description
BOOLEAN
Single point output
BOOLEAN
Data valid for single point output
BOOLEAN
Communication valid for single point output
BOOLEAN
Test output
Step
Default
-
Off
Section 3
Basic functions
Description
Operation Off/On
133