Section 3
Basic functions
3.7.5
56
IEC09000063 V1 EN
Figure 30:
Connection of the function to external circuits
The above example also includes five output signals, for confirmation of which group
that is active.

Application

Four sets of settings are available to optimize the IED operation for different system
conditions. By creating and switching between fine-tuned setting sets, either from the
LHMI or configurable binary inputs, results in a highly adaptable IED that can cope
with a variety of system scenarios.
Different conditions in networks with different voltage levels require highly adaptable
protection and control units to best provide for dependability, security and selectivity
requirements. Protection units operate with a higher degree of availability, especially,
if the setting values of their parameters are continuously optimized according to the
conditions in the power system.
Operational departments can plan for different operating conditions in the primary
equipment. The protection engineer can prepare the necessary optimized and pre-
tested settings in advance for different protection functions. Four different groups of
setting parameters are available in the IED. Any of them can be activated through the
different programmable binary inputs by external or internal control signals.
ACTIVATE GROUP 4
ACTIVATE GROUP 3
ACTIVATE GROUP 2
ACTIVATE GROUP 1
IOx-Bly1
Æ
IOx-Bly2
Æ
IOx-Bly3
Æ
IOx-Bly4
Æ
PML630/Compact Load-Shedding Solution
1MRS757256 F
ACTVGRP
ACTGRP1
GRP1
ACTGRP2
GRP2
ACTGRP3
GRP3
GRP4
ACTGRP4
SETCHGD
IEC09000063_en_1.vsd
Technical Manual