Settings - ABB RELION 630 Series Technical Manual

Power management
Hide thumbs Also See for RELION 630 Series:
Table of Contents

Advertisement

1MRS757256 F
7.4.6
Table 273:
PSCSWI Group settings (basic)
Name
Values (Range)
Start value
Start value Mult
Time multiplier
Operating curve type
Operate delay time
Table 274:
PSCSWI Group settings (advanced)
Name
Values (Range)
Type of reset curve
Table 275:
PSCSWI Non group settings (basic)
Name
Values (Range)
Block override
Maximum Ava power
Governor mode
Table continues on next page
PML630/Compact Load-Shedding Solution
Technical Manual

Settings

Unit
0.05 - 5.00
pu
0.8 - 10.0
-
0.05 - 15.00
-
ANSI Ext. inv.
-
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Programmable
RI type
RD type
0.04 - 200.00
s
Unit
Immediate
-
Def time reset
Inverse reset
Unit
No
-
IED test mode
Quality bad CB
close
Quality bad CB
open
CB Interm or invalid
All yes
0.0 - 999999.9
kW
Droop
-
MW
ISO
P-Control
Optimize
Base load
Peak load
Power management functions
Step
Default
0.01
0.05
0.1
1.0
0.05
1.00
-
IEC Def. Time
0.01
0.04
Step
Default
-
Immediate
Step
Default
-
No
0.1
0.0
-
ISO
Section 7
Description
Start value
Multiplier for scaling the start value
Time multiplier in IEC/ANSI curves
Selection of time delay curve type
Operate delay time
Description
Selection of reset curve type
Description
Bypass block due to IED test or data
quality or CB position
Maximum available power of power
source
Governor mode of generator
231