Binary To Integer Module - ABB RELION 630 Series Technical Manual

Power management
Hide thumbs Also See for RELION 630 Series:
Table of Contents

Advertisement

Section 7
Power management functions
7.4.4.9
228
The outputs AVA_POWER and ACTIVE_POWER are reported for the monitoring
view.
The ACTIVE_POWER (active power), slow load-shedding start and slow load trigger
inhibition signals are reported to the Binary to Integer module.

Binary to integer module

The DATA_SOURCE output provides the load-shedding data for the power source.
The data is also available in the monitoring view.
The DATA_SOURCE output consists of various binary information as shown in
269.
Based on the Source configure setting, the Binary to integer module calculates the
power source configuration status.
If the Source configure setting is set to "Generator", the power source configuration
status is FALSE. If the Source configure setting is set to "External source", the power
source configuration status is TRUE.
If the ACTIVE_POWER output is positive, the overcurrent operation status, maximum
demand operation status and external slow load-shedding trigger remain same as
received from the respective modules.
If the ACTIVE_POWER output is negative, the overcurrent operation status,
maximum demand operation status and external slow load-shedding trigger are
FALSE.
If the CB_COMPS_POS output is "Close", the compensated circuit breaker close
status is TRUE, else compensated circuit breaker close status is FALSE. If the
CB_COMPS_POS output is "Open" and FLS_TRIGGER is TRUE, the compensated
circuit breaker open status is FALSE.
Irrespective of the CB_COMPS_POS output, the compensated circuit breaker open
status is TRUE if the FLS_TRIGGER is FALSE.
Table 269:
DATA_SOURCE bits information
Bits
Bit Description
1
Source configuration
2
Compensated CB closed status
3
Fast load-shedding trigger
4
Fast load-shed block
5
Island parallel status
6
Overcurrent operating status
7
Slow load-shed start
8
Maximum demand operating status
Table continues on next page
Short name of signal
SOURCE_CONFIG
COMP_CB_CLS
FLS_TRIGGER
FLS_BLOCK
ISLAND_PARALL
OC_OPR
SLOWLS_STR
MAX_DMD_ALM
PML630/Compact Load-Shedding Solution
Technical Manual
1MRS757256 F
Table