Settings; Goose Function Block To Receive An Integer Value Gooseintrcv; Function Block; Functionality - ABB RELION 630 Series Technical Manual

Power management
Hide thumbs Also See for RELION 630 Series:
Table of Contents

Advertisement

1MRS757256 F
3.23.5
Table 93:
GOOSEDPRCV Non group settings (basic)
Name
Values (Range)
Operation
3.24
3.24.1
3.24.2
3.24.3
PML630/Compact Load-Shedding Solution
Technical Manual
Table 92:
GOOSEDPRCV Output signals
Name
DPOUT
DATAVALID
COMMVALID
TEST

Settings

Unit
Off
-
On
GOOSE function block to receive an integer value
GOOSEINTRCV

Function block

GOOSEINTRCV
BLOCK
^INTOUT
DATAVALID
COMMVALID
IEC10000250-1-en.vsd
IEC10000250 V1 EN
Figure 66:
Function block

Functionality

GOOSEINTRCV is used to receive an integer value using IEC61850 protocol via
GOOSE.

Operation principle

The DATAVALID output is HIGH if the incoming message is with valid data.
The COMMVALID output becomes LOW when the sending IED is under total failure
condition and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
Type
Description
INTEGER
Double point output
BOOLEAN
Data valid for double point output
BOOLEAN
Communication valid for double point output
BOOLEAN
Test output
Step
Default
-
Off
TEST
Section 3
Basic functions
Description
Operation Off/On
127

Advertisement

Table of Contents
loading