Function Block; Functionality; Operation Principle - ABB RELION 630 Series Technical Manual

Power management
Hide thumbs Also See for RELION 630 Series:
Table of Contents

Advertisement

Section 7
Power management functions
7.11.2
7.11.3
7.11.4
312

Function block

PPLSGGIO
PPLS
PEER_CB_STS
NW_PPLS
PEER_SR_STS
PEER_MS_STS
PEER_SRC_BLK
PEER_SN_BLK
PEER_DATA_ER
LS_DATA_ER
GUID-44A61373-A7B1-43FE-988F-A7DCEA69715C V1 EN
Figure 162:
Function block

Functionality

PPLSGGIO is the output interface for the load-shedding data for an adjacent electrical
area connected with the power source. The load-shedding information is converted
into weighted integer data. This function also provides outputs for the load-shedding
information received from the corresponding connected electrical area.

Operation principle

The operation of PPLSGGIO can be described by using a module diagram. All the
modules in the diagram are explained in the next sections.
PPLS
NW_PPLS
GUID-20810C87-7915-4691-B9DD-5BE26E2B4BD4 V1 EN
Figure 163:
Functional module diagram
PPLSGGIO receives the different load-shedding data of the subnetwork from
LSCACLS through the group input PPLS.
PPLSGGIO receives the circuit breaker information for external connection and load-
shedding data of the connected adjacent electrical area from NPMMXU function
through the group input NW_PPLS.
LS_DATA
LS_DATA_ER
PEER_CB_STS
PEER_SR_STS
PEER_MS_STS
General
logic
PEER_SRC_BLK
PEER_SN_BLK
PEER_DATA_ER
PEER_SP_RSV
PEER_MUST_LS
PML630/Compact Load-Shedding Solution
1MRS757256 F
Technical Manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pml630

Table of Contents