Source1/Source2 Ls Data Handle - ABB RELION 630 Series Technical Manual

Power management
Hide thumbs Also See for RELION 630 Series:
Table of Contents

Advertisement

Section 7
Power management functions
7.7.4.4
266
All conditions for processing the must-shedding status hold good.
The overcurrent operate status for power source 1, that is, OC_OPR_SRC1 is
FALSE.
The maximum demand operate status for power source 1, that is,
MAX_DMD_SRC1 is FALSE.
The external slow load-shed trigger for power source 1, that is, EXT_SLT_SRC1
is FALSE.
If any of the above conditions is not satisfied, the power balance status is FALSE.
The logic is identical for processing the PPLS2_DATA input and its
power balance status and must-shedding status.
The processed inputs PPLS1_DATA and PPLS2_DATA are provided as
PEER1_DATA and PEER2_DATA respectively.
corresponding signal name for PEER1_DATA and PEER2_DATA.
Table 307:
The bits description for PEER1_DATA AND PEER2_DATA
Bit No
Signal name for PEER1_DATA
1
RCV_CB_STS1
2
RCV_SR_STS1
3
RCV_MS_STS1
5 .. 29
RCV_LS_POW1
30
RCV_CB_BLK1
31
LS_BLK_STS1
The module provides the PEER1_DATA and PEER2_DATA to Source1/source2 LS
data handle module, Power monitoring module and Load shedding sharing mode
logic module.

Source1/source2 LS data handle

Based on the different conditions, the module calculates the compensated circuit
breaker status, island parallel status, fast load-shedding blocking status, circuit
breaker blocking status and fast load-shedding trigger for power source 1 and power
source 2.
1MRS757256 F
Table 307
shows the bits and
Signal name for PEER2_DATA
RCV_CB_STS2
RCV_SR_STS2
RCV_MS_STS2
RCV_LS_POW2
RCV_CB_BLK2
LS_BLK_STS2
PML630/Compact Load-Shedding Solution
Technical Manual