1MRS757256 F
10.2.3
PML630/Compact Load-Shedding Solution
Technical Manual
Binary inputs
The binary inputs can be used, for example, for status indications, to generate a
blocking signal, to unlatch output contacts, to trigger the disturbance recorder or for
remote control of IED settings.
Each signal connector terminal is dimensioned for one 0.5...2.5 mm
2
0.5...1.0 mm
wires.
Use only DC power for the binary inputs. Use of AC power, including
full- or half-wave rectified AC power, may cause damage to the binary
input modules.
Table 359:
Binary inputs X304,4U half 19"
Terminal
Description
X304-1
Common - for inputs 1-4
X304-2
Binary input 1 +
X304-3
Binary input 2 +
X304-4
Binary input 3 +
X304-5
Binary input 4 +
X304-6
Common - for inputs 5-8
X304-7
Binary input 5 +
X304-8
Binary input 6 +
X304-9
Binary input 7 +
X304-10
Binary input 8 +
X304-11
Common - for inputs 9-11
X304-12
Binary input 9 +
X304-13
Binary input 10 +
X304-14
Binary input 11 +
X304-15
Common - for inputs 12-14
X304-16
Binary input 12 +
X304-17
Binary input 13 +
X304-18
Binary input 14 +
Device's physical connections
ACT info
Hardware module
instance
COM_101
COM_101
COM_101
COM_101
COM_101
COM_101
COM_101
COM_101
COM_101
COM_101
COM_101
COM_101
COM_101
COM_101
Section 10
2
wire or for two
Hardware channel
BI1
BI2
BI3
BI4
BI5
BI6
BI7
BI8
BI9
BI10
BI11
BI12
BI13
BI14
357