Binary inputs

The binary inputs can be used, for example, for status indications, to generate a
blocking signal, to unlatch output contacts, to trigger the disturbance recorder or for
remote control of IED settings.
Each signal connector terminal is dimensioned for one 0.5...2.5 mm
2
0.5...1.0 mm
wires.
Use only DC power for the binary inputs. Use of AC power, including
full- or half-wave rectified AC power, may cause damage to the binary
input modules.
Table 359:
Binary inputs X304,4U half 19"
Terminal
Description
X304-1
Common - for inputs 1-4
X304-2
Binary input 1 +
X304-3
Binary input 2 +
X304-4
Binary input 3 +
X304-5
Binary input 4 +
X304-6
Common - for inputs 5-8
X304-7
Binary input 5 +
X304-8
Binary input 6 +
X304-9
Binary input 7 +
X304-10
Binary input 8 +
X304-11
Common - for inputs 9-11
X304-12
Binary input 9 +
X304-13
Binary input 10 +
X304-14
Binary input 11 +
X304-15
Common - for inputs 12-14
X304-16
Binary input 12 +
X304-17
Binary input 13 +
X304-18
Binary input 14 +
Device's physical connections
ACT info
Hardware module
instance
COM_101
COM_101
COM_101
COM_101
COM_101
COM_101
COM_101
COM_101
COM_101
COM_101
COM_101
COM_101
COM_101
COM_101
Section 10
2
wire or for two
Hardware channel
BI1
BI2
BI3
BI4
BI5
BI6
BI7
BI8
BI9
BI10
BI11
BI12
BI13
BI14
357

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pml630

Table of Contents