Table 366:
Signal output and IRF output
Description
Rated voltage
Continuous contact carry
Make and carry for 3.0 s
Make and carry 0.5 s
Breaking capacity when the control-circuit time
constant L/R<40 ms, at U< 48/110/220 V DC
Minimum contact load
Table 367:
Ethernet interfaces
Ethernet interface
Protocol
LAN1 (X1)
TCP/IP protocol
Table 368:
LAN (X1) fibre-optic communication link
Wave length
Fibre type
1300 nm
MM 62.5/125
μm or MM
50/125 μm
glass fibre
core
1) Maximum allowed attenuation caused by connectors and cable together
Table 369:
X4/IRIG-B interface
Type
Protocol
Screw terminal, pin row
IRIG-B
header
Table 370:
X9 Optical serial interface characteristics
Wave length
Fibre type
820 nm
MM 62.5/125
820 mm
MM 50/125
660 mm
1 mm
Value
250 V AC/DC
5 A
10 A
15 A
≤0.5 A/≤0.1 A/≤0.04 A
100 mA at 24 V AC/DC
Cable
Fibre-optic cable with
LC connector or
shielded twisted pair
CAT 5e cable or better
Connector
Permitted path
1)
attenuation
LC
<7.5 dB
Cable
Shielded twisted pair cable
Recommended: CAT 5, Belden RS-485 (9841-
9844) or Alpha Wire (Alpha 6222-6230)
Connector
Permitted path
attenuation
ST
4 dB/km
ST
4 dB/km
Snap-in
Section 11
Technical data
Data transfer rate
100 MBits/s
Distance
2 km
Distance
1000 m
400 m
10 m