Settings - ABB RELION 630 Series Technical Manual

Power management
Hide thumbs Also See for RELION 630 Series:
Table of Contents

Advertisement

Section 6
Measurement functions
6.1.4
Table 252:
CMMXU Non group settings (basic)
Name
Operation
A deadband PhA
A Hi high Lim PhA
A high limit PhA
A low limit PhA
A low low Lim PhA
A minimum PhA
A maximum PhA
A Db type PhA
A deadband PhB
A Hi high Lim PhB
A high limit PhB
A low limit PhB
A low low Lim PhB
A minimum PhB
A maximum PhB
A Db type PhB
A deadband PhC
A Hi high Lim PhC
A high limit PhC
Table continues on next page
198
Name
I_INST_B
I_DB_B
I_ANGL_B
I_RANGE_B
I_INST_C
I_DB_C
I_ANGL_C
I_RANGE_C

Settings

Values (Range)
Unit
Off
-
On
1 - 300
Type
0.0 - 100000.0
A
0.0 - 100000.0
A
0.0 - 100000.0
A
0.0 - 100000.0
A
0.0 - 100000.0
A
0.0 - 100000.0
A
Cyclic
-
Dead band
Int deadband
1 - 300
Type
0.0 - 100000.0
A
0.0 - 100000.0
A
0.0 - 100000.0
A
0.0 - 100000.0
A
0.0 - 100000.0
A
0.0 - 100000.0
A
Cyclic
-
Dead band
Int deadband
1 - 300
Type
0.0 - 100000.0
A
0.0 - 100000.0
A
Type
Description
REAL
Phase B amplitude, magnitude of instantaneous
value
REAL
Phase B amplitude, magnitude of reported value
REAL
Phase B angle, instantaneous value
INTEGER
Phase B amplitude range
REAL
Phase C amplitude, magnitude of instantaneous
value
REAL
Phase C amplitude, magnitude of reported value
REAL
Phase C angle, instantaneous value
INTEGER
Phase C amplitude range
Step
Default
-
On
1
10
0.1
500.0
0.1
400.0
0.1
0.0
0.1
0.0
0.1
0.0
0.1
500.0
-
Cyclic
1
10
0.1
500.0
0.1
400.0
0.1
0.0
0.1
0.0
0.1
0.0
0.1
500.0
-
Cyclic
1
10
0.1
500.0
0.1
400.0
1MRS757256 F
Description
Operation On / Off
Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
High High limit (physical value)
High limit (physical value)
Low limit (physical value)
Low Low limit (physical value)
Minimum value
Maximum value
Reporting type
Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
High High limit (physical value)
High limit (physical value)
Low limit (physical value)
Low Low limit (physical value)
Minimum value
Maximum value
Reporting type
Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
High High limit (physical value)
High limit (physical value)
PML630/Compact Load-Shedding Solution
Technical Manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pml630

Table of Contents