Settings - ABB RELION 630 Series Technical Manual

Power management
Hide thumbs Also See for RELION 630 Series:
Table of Contents

Advertisement

1MRS757256 F
7.8.6
Table 333:
LSCACLS Non group settings (basic)
Name
Values (Range)
Disable LS SubNetw
Enable LS SubNetw1
Enable LS SubNetw2
Enable LS SubNetw3
Enable LS SubNetw4
SubNetw1 Man Prio
SubNetw2 Man Prio
SubNetw3 Man Prio
SubNetw4 Man Prio
SubNetw1 Man Pow
SubNetw2 Man Pow
SubNetw3 Man Pow
SubNetw4 Man Pow
Table 334:
LSCACLS Non group settings (advanced)
Name
Values (Range)
Operation
SubNetw Abs offset
SubNetw Rel offset
Man load shed mode
PML630/Compact Load-Shedding Solution
Technical Manual

Settings

Unit
Yes
-
No
No
-
Yes
No
-
Yes
No
-
Yes
No
-
Yes
0 - 19
-
0 - 19
-
0 - 19
-
0 - 19
-
0.0 - 999999.9
kW
0.0 - 999999.9
kW
0.0 - 999999.9
kW
0.0 - 999999.9
kW
Unit
Off
-
On
-1000.00 - 1000.00
kW
-100.0 - 100.0
%
Disable manual LS
-
SN Man Prio setting
SN Man Pow
setting
SN Man Prio input
SN Man Pow input
Power management functions
Step
Default
-
No
-
Yes
-
Yes
-
Yes
-
Yes
1
0
1
0
1
0
1
0
0.1
0.0
0.1
0.0
0.1
0.0
0.1
0.0
Step
Default
-
Off
0.01
0.0
1.0
0.0
-
Disable manual LS
Section 7
Description
Disable load-shedding in all subneworks
Enable load-shedding in subnetwork 1
Enable load-shedding in subnetwork 2
Enable load-shedding in subnetwork 3
Enable load-shedding in subnetwork 4
Manual load shed priority for subnetwork
1
Manual load shed priority for subnetwork
2
Manual load shed priority for subnetwork
3
Manual load shed priority for subnetwork
4
Manual load shed power in kilo watt for
subnetwork 1
Manual load shed power in kilo watt for
subnetwork 2
Manual load shed power in kilo watt for
subnetwork 3
Manual load shed power in kilo watt for
subnetwork 4
Description
Operation Mode Off / On
Absolute safety margin for power balance
Relative safety margin for power balance
Manual load shed mode selection
299