Signals - ABB RELION 630 Series Technical Manual

Power management
Hide thumbs Also See for RELION 630 Series:
Table of Contents

Advertisement

Section 7
Power management functions
7.7.5
274
Table 317:
The group signals for NW_PPLS2
Signal description
Load-shed data of adjacent area connected with power
source 2
Fast load-shed CB blocking status for power source 2
Compensated CB open status for power source 2

Signals

Table 318:
NPMMXU Input signals
Name
Type
SOURCE1
GROUP
SIGNAL
SOURCE2
GROUP
SIGNAL
SOURCE3
GROUP
SIGNAL
SOURCE4
GROUP
SIGNAL
SOURCE5
GROUP
SIGNAL
SOURCE6
GROUP
SIGNAL
SOURCE7
GROUP
SIGNAL
SOURCE8
GROUP
SIGNAL
SLS_TRG_INH
BOOLEAN
PPLS1_DATA
INTEGER
PPLS1_QVAL
BOOLEAN
PPLS1_TEST
BOOLEAN
PPLS2_DATA
INTEGER
PPLS2_QVAL
BOOLEAN
PPLS2_TEST
BOOLEAN
TEST
BOOLEAN
Group signal NW_PPLS2
PPLS2_DATA
CB_BLK_SRC2
CCB_OPN_SRC2
Default
Description
-
Group signal from power source 1
-
Group signal from power source 2
-
Group signal from power source 3
-
Group signal from power source 4
-
Group signal from power source 5
-
Group signal from power source 6
-
Group signal from power source 7
-
Group signal from power source 8
0
Slow load shed trigger inhibit
0
LS data of electrical area connected with power
source 1
0
Data quality of electrical area connected with
power source 1
0
Electrical area PML test mode connected with
power source 1
0
LS data of electrical area connected with power
source 2
0
Data quality of electrical area connected with
power source 2
0
Electrical area PML test mode connected with
power source 2
0
Test mode behaviour of PML IED