Settings; Measured Values - ABB RELION 630 Series Technical Manual

Power management
Hide thumbs Also See for RELION 630 Series:
Table of Contents

Advertisement

Section 5
Supervision functions
5.1.7
Table 245:
SPVNZBAT Non group settings (basic)
Name
Operation
Battery voltage Rtg
Low battery value
High battery value
Alarm delay time
Table 246:
SPVNZBAT Non group settings (advanced)
Name
Reset delay time
5.1.8
194
Table 244:
SPVNZBAT Output signals
Name
AL_ULOW
AL_UHIGH
ST_ULOW
ST_UHIGH

Settings

Values (Range)
Unit
Off
-
On
20.00 - 250.00
V
0.60 - 1.40
pu
0.60 - 1.40
pu
0.100 - 60.000
s
Values (Range)
Unit
0.000 - 60.000
s

Measured values

Table 247:
SPVNZBAT Measured values
Name
U_BATT_IN
BLOCK
BLK_AL
BLK_ST
Type
Description
BOOLEAN
Alarm when voltage has been below lower limit for
a set time
BOOLEAN
Alarm when voltage has exceeded higher limit for a
set time
BOOLEAN
Start signal when battery voltage drops below
lower limit
BOOLEAN
Start signal when battery voltage exceeds upper
limit
Step
Default
-
On
1.00
110.00
0.01
0.70
0.01
1.20
0.001
0.200
Step
Default
0.001
0.000
Type
Default
Description
REAL
0.00
Battery terminal voltage
BOOLEAN
0
Block of function
BOOLEAN
0
Blocks the alarm signals
BOOLEAN
0
Blocks the start signals
1MRS757256 F
Description
Operation Off/On
Battery rated voltage
Lower limit for the battery terminal voltage
Upper limit for the battery terminal voltage
Delay time for alarm
Description
Reset time provided to reset the timers
PML630/Compact Load-Shedding Solution
Technical Manual