Technical data

Table 78:
IEC 61850-8-1 communication protocol
Function
Protocol
Communication speed for the IEDs
Protocol
Communication speed for the IEDs
Protocol
Communication speed for the IEDs
Protocol
Communication speed for the IEDs

GOOSE receive GOOSEPWRFDRRCV

Function block

GOOSEPWRFDRRCV
BLOCK
SPSOUT1
SPSDATAVALID1
SPSCOMMVALID1
SPSOUT2
SPSDATAVALID2
SPSCOMMVALID2
DPSOUT
DPSDATAVALID
DPSCOMMVALID
MVOUT
MVDATAVALID
MVCOMMVALID
DATAVALID
COMMVALID
TEST
GUID-58C26A98-D670-4723-8BBE-B04C0B2C8938 V1 EN
Figure 61:
Function block

Functionality

GOOSEPWRFDRRCV is a GOOSE receive function block used for receiving a set of
data from IEDs associated with load shed and network circuit breakers, required to
handle the load shedding functionality.

Signals

Table 79:
GOOSEPWRFDRRCV Input signals
Name
Type
BLOCK
BOOLEAN
Value
IEC 61850-8-1
100BASE-FX
IEC 608–5–103
9600 or 19200 Bd
DNP3.0
300–19200 Bd
TCP/IP, Ethernet
100 Mbit/s
Default
Description
0
Block of output signals
PML630/Compact Load-Shedding Solution
1MRS757256 F
Technical Manual