Section 3
Basic functions
3.24.4
3.24.5
Table 96:
GOOSEINTRCV Non group settings (basic)
Name
Operation
128
The input of this GOOSE block must be linked in Signal Matrix by
means of a cross to receive the integer values.
The implementation for IEC 61850 quality data handling is restricted
to a simple level. If quality data validity is GOOD, the DATAVALID
output is HIGH. If quality data validity is INVALID,
QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA, the
DATAVALID output is LOW.

Signals

Table 94:
GOOSEINTRCV Input signals
Name
BLOCK
Table 95:
GOOSEINTRCV Output signals
Name
INTOUT
DATAVALID
COMMVALID
TEST

Settings

Values (Range)
Unit
Off
-
On
Type
Default
Description
BOOLEAN
0
Block of function
Type
Description
INTEGER
Integer output
BOOLEAN
Data valid for integer output
BOOLEAN
Communication valid for integer output
BOOLEAN
Test output
Step
Default
-
Off
1MRS757256 F
Description
Operation Off/On
PML630/Compact Load-Shedding Solution