1MRS757256 F
3.14.1.5
3.14.1.6
Table 47:
DRRDRE Non group settings (basic)
Name
Values (Range)
Operation
Pre-trigger time
Post-trigger time
Recording time limit
Post-retrig
Max Num records
Reference channel
Operation mode test
3.14.1.7
PML630/Compact Load-Shedding Solution
Technical Manual
Signals
Table 46:
DRRDRE Output signals
Name
DRPOFF
RECSTART
RECMADE
CLEARED
MEMUSED
Settings
Unit
Off
-
On
0.05 - 3.00
s
0.1 - 10.0
s
0.5 - 8.0
s
Off
-
On
10 - 100
-
1 - 30
Ch
Off
-
On
Monitored data
Table 48:
DRRDRE Monitored data
Name
DRPOFF
RECSTART
RECMADE
CLEARED
MEMUSED
Memory used
Fault number
Type
Description
BOOLEAN
Disturbance report function turned off
BOOLEAN
Disturbance recording started
BOOLEAN
Disturbance recording made
BOOLEAN
All disturbances in the disturbance report cleared
BOOLEAN
More than 80% of memory used
Step
Default
-
Off
0.01
0.10
0.1
0.5
0.1
1.0
-
Off
1
100
1
1
-
Off
Type
Values (Range)
BOOLEAN
0=FALSE
1=TRUE
BOOLEAN
0=FALSE
1=TRUE
BOOLEAN
0=FALSE
1=TRUE
BOOLEAN
0=FALSE
1=TRUE
BOOLEAN
0=FALSE
1=TRUE
INTEGER
-
INTEGER
-
Section 3
Basic functions
Description
Operation Off/On
Pre-fault recording time
Post-fault recording time
Fault recording time limit
Post-fault retrig enabled (On) or not (Off)
Maximum number of stored disturbances
Trip value recorder, phasor reference
channel
Operation mode during test mode
Unit
Description
-
Disturbance report
function turned off
-
Disturbance recording
started
-
Disturbance recording
made
-
All disturbances in the
disturbance report
cleared
-
More than 80% of
memory used
%
Memory usage (0-100%)
-
Disturbance fault number
85