Section 3
Basic functions
3.32.1.17
156
Functionality
The function compares the integer inputs INT_IN1 and INT_IN2 and activates the
binary output OUTPUT, if INT_IN1 is greater than or equal to INT_IN2.
If INT_IN1 ≥ INT_IN2, OUTPUT = 1, else OUTPUT = 0.
Logic function blocks do not have the hysteresis feature. Oscillating
outputs should be avoided when comparing analog signals that have
very closely varying values.
Signals
Table 156:
GEI Input signals
Name
Type
INT_IN1
INTEGER
INT_IN2
INTEGER
Table 157:
GEI Output signals
Name
Type
OUTPUT
BOOLEAN

Less than check for real signals LTR

Function block
GUID-853AED74-6085-4A2C-AA93-8890593A483C V1 EN
Figure 91:
Function block
Functionality
The function compares the real inputs REAL_IN1 and REAL_IN2 and activates the
binary output OUTPUT, if REAL_IN1 is less than REAL_IN2.
If REAL_IN1 < REAL_IN2, OUTPUT = 1, else OUTPUT = 0.
Logic function blocks do not have the hysteresis feature. Oscillating
outputs should be avoided when comparing analog signals that have
very closely varying values.
Default
Description
0
Integer input 1
0
Integer input 2
Description
Binary output
PML630/Compact Load-Shedding Solution