Section 12 Device And Functionality Tests - ABB RELION 630 Series Technical Manual

Power management
Hide thumbs Also See for RELION 630 Series:
Table of Contents

Advertisement

1MRS757256 F
Section 12
PML630/Compact Load-Shedding Solution
Technical Manual
Device and functionality tests
Table 375:
Electromagnetic compatibility tests
Description
100 kHz and 1 MHz burst
disturbance test
Common mode
Differential mode
3 MHz, 10 MHz and 30 MHz
burst disturbance test
Common mode
Electrostatic discharge test
Contact discharge
Air discharge
Radio frequency interference
tests
Conducted, common
mode
Radiated, pulse-
modulated
Radiated, amplitude-
modulated
Fast transient disturbance tests
All ports
Surge immunity test
Communication
Binary inputs, voltage
inputs
Other ports
Power frequency (50 Hz)
magnetic field
Table continues on next page
Device and functionality tests
Type test value
2.5 kV
1.0 kV
2.5 kV
8 kV
15 kV
10 V (rms), f=150 kHz...80 MHz
10 V/m (rms), f=900 MHz
10 V/m (rms), f=80...2700 MHz
4 kV
1 kV line-to-earth
2 kV line-to-earth
1 kV line-to-line
4 kV line-to-earth, 2 kV line-to-
line
Section 12
Reference
IEC 61000-4-18, level 3
IEC 60255-22-1
IEC 61000-4-18
IEC 60255-22-1, class III
IEC 61000-4-2, level 4
IEC 60255-22-2
IEEE C37.90.3.2001
IEC 61000-4-6 , level 3
IEC 60255-22-6
ENV 50204
IEC 60255-22-3
IEC 61000-4-3, level 3
IEC 60255-22-3
IEC 61000-4-4
IEC 60255-22-4, class A
IEC 61000-4-5, level 3/2
IEC 60255-22-5
IEC 61000-4-8
365