Signals - ABB RELION 630 Series Technical Manual

Power management
Hide thumbs Also See for RELION 630 Series:
Table of Contents

Advertisement

Section 7
Power management functions
7.4.5
230

Signals

Table 271:
PSCSWI Input signals
Name
Type
I_A
REAL
I_B
REAL
I_C
REAL
POWER
REAL
CB_POSITION
INTEGER
CB_SERVICE
BOOLEAN
CB_LOCK_OUT
BOOLEAN
CB_IED_QVAL
BOOLEAN
IED_TST_MODE
BOOLEAN
MAX_POWER
REAL
GOVERNOR_MOD
INTEGER
AP_GOV_QVAL
BOOLEAN
ISLAND_PARAL
BOOLEAN
ENA_MULT
BOOLEAN
EXT_OC_SLST
BOOLEAN
INHIBIT_TRG
BOOLEAN
SLS_DISABLE
BOOLEAN
RESET_OC
BOOLEAN
RESET_DEMAND
BOOLEAN
Table 272:
PSCSWI Output signals
Name
Type
SOURCE
GROUP SIGNAL
CB_COMPS_POS
INTEGER
ACTIVE_POWER
REAL
AVA_POWER
REAL
FLS_TRIGGER
BOOLEAN
SLOWLS_OPR
BOOLEAN
OC_STR
BOOLEAN
OC_OPR
BOOLEAN
MAX_DMD_ALM
BOOLEAN
ISLND_PARALL
BOOLEAN
FLS_BLOCK
BOOLEAN
BLK_BYPASS
BOOLEAN
B_SET_CHANGE
BOOLEAN
INVAL_CRV
BOOLEAN
Default
Description
0.0
Phase A RMS current of power source
0.0
Phase B RMS current of power source
0.0
Phase C RMS current of power source
0.0
Active power from power source
1
Circuit breaker position of source
0
Circuit breaker service position of power source
0
Circuit breaker lockout status of power source
1
Circuit breaker IED quality status of power source
0
IED test mode behaviour of power source
0.0
Available power of power source on
communication
3
Governor mode of generator on communication
1
Quality status of available power and governor
mode on comm
1
Island or parallel mode for external power source
0
Enable signal for current multiplier
0
External slow load shed trigger for power source
0
Inhibit the trigger from power source
0
Slow load shed disable of power source
0
Reset for over current
0
Reset for maximum demand
Description
Group signal of power source
Circuit breaker position of power source
Active power of power source
Available power of power source
Fast load shed trigger from power source
Slow load shed trigger from power source
Over current start of power source
Over current operate status of power source
Max demand operate alarm for power source
Island or parallel mode status of external source
Fast load shed block from power source
Block is bypassed
One or many basic setting change
Invalid curve parameters
PML630/Compact Load-Shedding Solution
1MRS757256 F
Technical Manual