Monitored Data - ABB RELION 630 Series Technical Manual

Power management
Hide thumbs Also See for RELION 630 Series:
Table of Contents

Advertisement

Section 7
Power management functions
7.4.8
234

Monitored data

Table 278:
PSCSWI Monitored data
Name
Type
DATA_SOURCE
INTEGER
CB_COMPS_POS
INTEGER
ACTIVE_POWER
REAL
AVA_POWER
REAL
GOV_MODE
INTEGER
AVG_DEMAND
REAL
PERIODIC_KWH
REAL
MAX_CURRENT
REAL
OVLOD_AMOUNT
REAL
PICKUP
REAL
ELAPSE_TIME
REAL
OC_TIME
REAL
SLOWLS_MODE
INTEGER
FLS_TRIGGER
BOOLEAN
SLOWLS_OPR
BOOLEAN
OC_STR
BOOLEAN
OC_OPR
BOOLEAN
MAX_DMD_ALM
BOOLEAN
Table continues on next page
Values (Range)
Unit
-
-
1=Open
-
2=Close
-
kW
-
kW
1=Droop
-
2=MW
3=ISO
4=P-Control
5=Optimize
6=Base load
7=Peak load
0=Not applicable
-
kW
-
kWh
-
A
-
kW
-
-
-
s
-
s
1=Disable
-
2=OC & Ext Trg
3=Max Dmd Trg
4=OC, Max Dmd,
Ext Trg
0=FALSE
-
1=TRUE
0=FALSE
-
1=TRUE
0=FALSE
-
1=TRUE
0=FALSE
-
1=TRUE
0=FALSE
-
1=TRUE
PML630/Compact Load-Shedding Solution
1MRS757256 F
Description
Load shed data for power
source
Circuit breaker position of
power source
Active power of power
source
Available power of power
source
Governor mode of
generator
Average demand over
set interval of power
source
Periodic energy at
demand interval of power
source
Maximum of three phase
current of power source
Overload amount during
slow load trigger
Pick up value for over
current start of power
source
Elapse time after
overcurrent start
Time require for over
current operate
Enable or disable signal
for curr and demand
based load shed
Fast load shed trigger
from power source
Slow load shed trigger
from power source
Over current start of
power source
Over current operate
status of power source
Max demand operate
alarm for power source
Technical Manual