Section 3
Basic functions
3.30.3
3.30.4
3.30.5
3.30.6
Table 111:
MVGGIO Non group settings (basic)
Name
BasePrefix
MV db
MV zeroDb
MV hhLim
MV hLim
Table continues on next page
138

Operation principle

Upon receiving an analog signal at its input, the IEC61850 generic communication I/
O functions (MVGGIO) give the instantaneous value of the signal and the range, as
output values. In the same time, it sends over IEC 61850-8-1 the value, to other IEC
61850 clients in the substation.

Application

IEC 61850 generic communication I/O functions (MVGGIO) function is used to send
the instantaneous value of an analog signal to other systems or equipment in the
substation. It can also be used inside the same IED, to attach a RANGE aspect to an
analog value and to permit measurement supervision on that value.

Signals

Table 109:
MVGGIO Input signals
Name
BLOCK
IN
Table 110:
MVGGIO Output signals
Name
VALUE
RANGE

Settings

Values (Range)
Unit
micro
-
milli
unit
kilo
Mega
Giga
Tera
1 - 300
Type
0 - 100000
m%
-5000.00 - 5000.00
xBase
-5000.00 - 5000.00
xBase
Type
Default
Description
BOOLEAN
0
Block of function
REAL
0
Analog input value
Type
Description
REAL
Magnitude of deadband value
INTEGER
Range
Step
Default
-
unit
1
10
1
500
0.01
900.00
0.01
800.00
1MRS757256 F
Description
Base prefix (multiplication factor)
Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
Zero point clamping in 0,001% of range
High High limit multiplied with the base
prefix (multiplication factor)
High limit multiplied with the base prefix
(multiplication factor)
PML630/Compact Load-Shedding Solution
Technical Manual