Settings - ABB RELION 630 Series Technical Manual

Power management
Hide thumbs Also See for RELION 630 Series:
Table of Contents

Advertisement

1MRS757256 F
3.8.3.2
Table 30:
SMAI_20_2 Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
DFTReference
ConnectionType
AnalogInputType
Table 31:
SMAI_20_2 Non group settings (advanced)
Name
Values (Range)
Negation
MinValFreqMeas
PML630/Compact Load-Shedding Solution
Technical Manual

Settings

Only values 1-3 of the parameter GlobalBaseSel should normally be
used. The values 1-3 refer to the global base value groups Phase Grp
1, Phase Grp 2 and Phase Grp 3 correspondingly (BASEPH1,
BASEPH2 and BASEPH3 in PCM600). The selection affects the
actual limit for frequency calculation set by MinValFreqMeas which
by default is 10% of the Voltage base Val PP in the selected group.
The values 4-6 refer to Residual Grp 1, Residual Grp 2 and Residual
Grp 3 (BASERES1, BASERES2 and BASERES3 in PCM600)
correspondingly and they are typically not to be used in this
connection.
Unit
1 - 6
-
InternalDFTRef
-
DFTRefGrp1
DFTRefGrp2
DFTRefGrp3
DFTRefGrp4
DFTRefGrp5
DFTRefGrp6
DFTRefGrp7
DFTRefGrp8
DFTRefGrp9
DFTRefGrp10
DFTRefGrp11
DFTRefGrp12
External DFT ref
Ph-N
-
Ph-Ph
Voltage
-
Current
Unit
Off
-
NegateN
Negate3Ph
Negate3Ph+N
5 - 200
%
Even if the AnalogInputType setting of a SMAI block is set to
Current, the MinValFreqMeas setting is still visible. This means that
the minimum level for current amplitude is based on Voltage base Val
PP. For example, if Voltage base Val PP is 20000, the minimum
amplitude for current is 20000 * 10% = 2000. This has practical affect
Step
Default
1
1
-
InternalDFTRef
-
Ph-N
-
Voltage
Step
Default
-
Off
1
10
Section 3
Basic functions
Description
Selection of one of the Global Base Value
groups
DFT reference
Input connection type
Analog input signal type
Description
Negation
61