Section 3
Basic functions
3.32.1.22
3.32.2
160
Table 167:
NER Output signals
Name
Type
OUTPUT
BOOLEAN
Not equal check for integer signals NEI
Function block
GUID-10E96EE1-8BCF-47AA-AD2F-BDA97D2B332F V1 EN
Figure 96:
Function block
Functionality
The function compares the integer inputs INT_IN1 and INT_IN2 and activates the
binary output OUTPUT, if INT_IN1 is not equal to INT_IN2.
If INT_IN1 ≠ INT_IN2, OUTPUT = 1, else OUTPUT = 0.
Logic function blocks do not have the hysteresis feature. Oscillating
outputs should be avoided when comparing analog signals that have
very closely varying values.
Signals
Table 168:
NEI Input signals
Name
Type
INT_IN1
INTEGER
INT_IN2
INTEGER
Table 169:
NEI Output signals
Name
Type
OUTPUT
BOOLEAN
Configurable logic Q/T
A number of logic blocks and timers with the capability to propagate timestamp and
quality of the input signals are available. The function blocks assist the user to adapt
the IEDs configuration to the specific application needs.
Description
Binary output
Default
Description
0
Integer input 1
0
Integer input 2
Description
Binary output
PML630/Compact Load-Shedding Solution
1MRS757256 F
Technical Manual