Section 7
Power management functions
7.10.6
310
Name
Type
DIF_MUST_ACT
REAL
MAN_SHD_POW
REAL
MAN_SHD_PRIO
INTEGER

Monitored data

Table 346:
SNWRCLS Monitored data
Name
Type
DISABLE_LS
BOOLEAN
SN_ACTIVE
BOOLEAN
LS_BLOCK
BOOLEAN
SLS_TRG_INH
BOOLEAN
NEG_POW_BAL
BOOLEAN
LS_RESET
BOOLEAN
MAN_LS_TRG
BOOLEAN
LS_OPERATE
BOOLEAN
LS_OPR_STS
INTEGER
AVA_POWER
REAL
RUNNING_LOAD
REAL
SHDABL_LOAD
REAL
POWER_BAL
REAL
EFF_POW_BAL
REAL
LOD_MISMATCH
REAL
MUST_SHD_LOD
REAL
ACT_SHD_LOD
REAL
Table continues on next page
Description
Difference between the must be load shed and
actual load shed
Manual load shed power settings
Manual load shed Priority settings
Values (Range)
Unit
0=FALSE
-
1=TRUE
0=FALSE
-
1=TRUE
0=FALSE
-
1=TRUE
0=FALSE
-
1=TRUE
0=FALSE
-
1=TRUE
0=FALSE
-
1=TRUE
0=FALSE
-
1=TRUE
0=FALSE
-
1=TRUE
0=No Load shed
-
1=Fast Load
shed
2=Slow Load
shed
3=Manual Load
shed
4=Plant level
Load shed
5=Extended
Load shed
-
kW
-
kW
-
kW
-
kW
-
kW
-
kW
-
kW
-
kW
PML630/Compact Load-Shedding Solution
1MRS757256 F
Description
Load shed disable
Subnetwork active status
Load shed block
Slow load shed trigger
inhibit
Negative power balance
status
Load shed reset
Manual load shed trigger
Load shed operate
Load shed operated
status
Total Available power
Total load
Total sheddable load
Power balance in the
subnetwork
Effective power balance
in the subnetwork
Total load mismatch
Must be load shed
Actually shed load
Technical Manual