3.29
3.29.1
3.29.2
3.29.3
PML630/Compact Load-Shedding Solution
Technical Manual
IEC 61850 generic communication I/O functions 16
inputs SP16GGIO

Function block

SP16GGIO

BLOCK
^IN1
^IN2
^IN3
^IN4
^IN5
^IN6
^IN7
^IN8
^IN9
^IN10
^IN11
^IN12
^IN13
^IN14
^IN15
^IN16
IEC09000238_en_1.vsd
IEC09000238 V1 EN
Figure 71:
Function block

Functionality

IEC 61850 generic communication I/O functions 16 inputs SP16GGIO function is
used to send up to 16 logical signals to other systems or equipment in the substation.

Operation principle

Upon receiving signals at its inputs, the IEC 61850 generic communication I/O
functions 16 inputs (SP16GGIO) function sends the signals over IEC 61850-8-1 to the
equipment or system that requests these signals. To be able to get the signal, one must
use other tools, described in the engineering manual and define which function block
in which equipment or system should receive this information.
There are also 16 output signals that show the input status for each input as well as an
OR type output combined for all 16 input signals. These output signals are handled in
the Parameter Setting tool.