Section 7
Power management functions
7.11.5
7.11.6
314
If PEER_SR_STS is TRUE, the spinning reserve of the adjacent electrical area is
provided by PEER_SP_RSV output. If PEER_SR_STS is FALSE, the
PEER_SP_RSV output is zero.
If PEER_MS_STS is TRUE, the must-shedding power of the adjacent electrical area
is provided by PEER_MUST_LS output. If the PEER_MS_STS is FALSE, the
PEER_MUST_LS output is zero.
Once PEER_MS_STS is TRUE, PEER_MUST_LS is on hold until the subnetwork is
reset. The PEER_MUST_LS is reset with activation of LS_RESET signal for
corresponding subnetwork.

Signals

Table 349:
PPLSGGIO Input signals
Name
Type
PPLS
GROUP
SIGNAL
NW_PPLS
GROUP
SIGNAL
Table 350:
PPLSGGIO Output signals
Name
Type
PEER_CB_STS
BOOLEAN
PEER_SR_STS
BOOLEAN
PEER_MS_STS
BOOLEAN
PEER_SRC_BLK
BOOLEAN
PEER_SN_BLK
BOOLEAN
PEER_DATA_ER
BOOLEAN
LS_DATA_ER
BOOLEAN

Monitored data

Table 351:
PPLSGGIO Monitored data
Name
Type
PEER_CB_STS
BOOLEAN
PEER_SR_STS
BOOLEAN
PEER_MS_STS
BOOLEAN
Table continues on next page
Default
Description
-
Group signal from load shed function
-
Group signal from network power source
Description
CB status of adjacent electrical area
Spinning reserve status of adjacent electrical area
Must shed status extended from adjacent electrical
area
Connectivity and CB block status of adjacent
electrical area
Subnetwork LS block status of adjacent electrical
area
Data error of adjacent electrical area
Load shed data error for adjacent electrical area
Values (Range)
Unit
0=Open
-
1=Close
0=FALSE
-
1=TRUE
0=FALSE
-
1=TRUE
PML630/Compact Load-Shedding Solution
1MRS757256 F
Description
CB status of adjacent
electrical area
Spinning reserve status
of adjacent electrical area
Must shed status
extended from adjacent
electrical area