Pulsetimer Function Block; Controllable Gate Function Block Gate - ABB RELION 630 Series Technical Manual

Power management
Hide thumbs Also See for RELION 630 Series:
Table of Contents

Advertisement

Section 3
Basic functions
3.32.1.3
Table 123:
PULSETIMER Non group settings (basic)
Name
t
3.32.1.4
144

PULSETIMER function block

Function block
PULSETIMER
INPUT
IEC09000291-1-en.vsd
IEC09000291 V1 EN
Figure 76:
Function block
Functionality
The pulse function can be used, for example for pulse extensions or limiting of
operation of outputs. The PULSETIMER has a settable length.
Signals
Table 121:
PULSETIMER Input signals
Name
INPUT
Table 122:
PULSETIMER Output signals
Name
OUT
Settings
Values (Range)
Unit
0.000 - 90000.000
s

Controllable gate function block GATE

Function block
GATE
INPUT
IEC09000295-1-en.vsd
IEC09000295 V1 EN
Figure 77:
Function block
Functionality
The GATE function block is used for controlling if a signal should pass from the input
to the output or not, depending on setting.
OUT
Type
Default
Description
BOOLEAN
0
Input signal
Type
Description
BOOLEAN
Output signal
Step
Default
0.001
0.010
OUT
1MRS757256 F
Description
Pulse time length
PML630/Compact Load-Shedding Solution
Technical Manual