ABB RELION 630 Series Technical Manual page 225

Power management
Hide thumbs Also See for RELION 630 Series:
Table of Contents

Advertisement

1MRS757256 F
PML630/Compact Load-Shedding Solution
Technical Manual
0
Load-shedding blocking = TRUE
Load-shedding blocking = FALSE
GUID-AC44FCB5-C8E0-4CF2-9608-CB82879B1244 V1 EN
Figure 132:
Logic for load-shedding blocking status at the time of measurement
cycle
0
Load-shedding blocking = TRUE
Load-shedding blocking = FALSE
GUID-82D266F7-DA92-4661-B1BA-8AC28635BD1F V1 EN
Figure 133:
Logic for load-shedding blocking status within the measurement
cycle
Where
q
CB_IED_QVAL
T, 2T, 3T
Measurement cycle
t
Time between the change of CB_IED_QVAL input from "Bad" to "Good" and the next
measurement cycle.
If the IED_TST_MODE input is TRUE or the CB_POSITION input is "Invalid", or
the CB_POSITION input remains in the "Intermediate" position for more than the CB
Interm time setting, the load-shedding blocking status is TRUE.
The load-shedding blocking status is reported to the General logic module, Fast load-
shedding trigger logic module, Slow load-shedding logic module, Over current based
load-shedding module and Demand based load-shedding module.
Power management functions
q = Bad
q = Good
T
2 T
t
q = Bad q = Good
T
2 T
Section 7
3 T
4 T
T
3 T
4 T
5 T
5 T
219