Application; Signals - ABB RELION 630 Series Technical Manual

Power management
Hide thumbs Also See for RELION 630 Series:
Table of Contents

Advertisement

1MRS757256 F
3.10.4
3.10.5
PML630/Compact Load-Shedding Solution
Technical Manual
The NEW_VAL signal is a pulse signal. The signal is set if the counter value was
updated since last report.
The SCAL_VAL signal consists of scaled value (according to parameter Scale), time
and status information.

Application

Pulse counter (PCGGIO) function counts externally generated binary pulses, for
instance pulses coming from an external energy meter, for calculation of energy
consumption values. The pulses are captured by the binary input module (BIO), and
read by the PCGGIO function. The number of pulses in the counter is reported via the
station bus to the substation automation system or read via the station monitoring
system as a service value. When using IEC 61850-8-1, a scaled service value is
available over the station bus.
The normal use for this function is the counting of energy pulses from external energy
meters. An optional number of inputs from the binary input module in IED can be used
for this purpose with a frequency of up to 35 Hz. PCGGIO can also be used as a general
purpose counter.

Signals

Table 35:
PCGGIO Input signals
Name
Type
BLOCK
BOOLEAN
READ_VAL
BOOLEAN
BI_PULSE
BOOLEAN
RS_CNT
BOOLEAN
Table 36:
PCGGIO Output signals
Name
Type
INVALID
BOOLEAN
RESTART
BOOLEAN
BLOCKED
BOOLEAN
NEW_VAL
BOOLEAN
SCAL_VAL
REAL
Default
Description
0
Block of function
0
Initiates an additional pulse counter reading
0
Connect binary input channel for metering
0
Resets pulse counter value
Description
The pulse counter value is invalid
The reported value does not comprise a complete
integration cycle
The pulse counter function is blocked
A new pulse counter value is generated
Scaled value with time and status information
Section 3
Basic functions
69