INVT Goodrive350-19 Series Operation Manual page 289

Hide thumbs Also See for Goodrive350-19 Series:
Table of Contents

Advertisement

Goodrive350-19 series VFD
Function
Name
code
unit
7.2.12 P11 Protection parameters
Function
Name
code
Phase-loss
P11.00
protection
Frequency-drop at
P11.01
transient power
down
P11.02
Energy braking
selection for stop
Overvoltage stall
P11.03
protection
Description
seconds;
1: min; the running time of each step is counted in
minutes;
Description
0x000–0x1111
Ones place: Reserved
Tens place:
0: Disable output phase loss protection
1: Enable output phase loss protection
Hundreds place:
0: Disable hardware input phase loss protection
1: Enable hardware input phase loss protection
Thousands place:
0: During stop, if a hardware input phase loss fault
occurs, it reports SPI.
1: During stop, if a hardware input phase loss fault
occurs, it reports A-SPI.
0: Disable
1: Enable
0: Enable
1: Disable
0: Disable
1: Enable
- 282 -
Function parameter list
Default
Modify
value
Default
Modify
value
Model
depended
0
0
0