Goodrive350-19 series VFD
correct factory password to enter the interface. (You are not advised to modify the factory
parameters. Incorrect parameter setting may cause operation exceptions or even damage to
the VFD.) When password protection does not take effect, you can change the password any
time. When P07.00 is set to 0, no user password is used. When P07.00 is set to a non-zero
value during VFD power-on, parameters are prevented from being modified by using the user
password function. When you modify function parameters through serial communication, the
user password protection function is also applicant and compliant with the same rule.
7.2.1 P00 Basic functions
Function
Name
code
Speed control
P00.00
mode
Running
P00.01
command
channel
Communication
P00.02
running command
channel
Max. output
P00.03
frequency
Upper limit of
P00.04
running frequency
Description
0: SVC 0
1: SVC 1
2: SVPWM
3: VC
Note: If 0, 1 or 3 is selected, it is required to carry
out motor parameter autotuning first.
0: Keypad
1: Terminal
2: Communication
0: MODBUS
1: PROFIBUS/CANopen/Devicenet
2: Ethernet
3: EtherCat/Profinet
4: PLC programmable card
5: Wireless communication card
Note: 1, 2, 3, 4 and 5 are extended functions
which are available only when corresponding
cards are used.
Used to set the maximum output frequency of the
VFD. It is the basis of frequency setup and the
acceleration/deceleration.
Setting range: Max. (P00.04, 10.00) –150.00Hz
The upper limit of running frequency is upper limit
value of VFD output frequency. This value cannot
be greater than the maximum output frequency.
- 202 -
Function parameter list
Default
Modify
value
2
0
0
50.00Hz