Goodrive350-19 series VFD
Function
Name
code
P01.23
Start delay
P01.24 Stop speed delay 0.0–600.0s
Open-loop 0Hz
P01.25
output selection
Deceleration time
P01.26
of
emergency-stop
Time of starting
section of
P01.27
deceleration S
curve
Time of ending
section of
P01.28
deceleration S
curve
Short-circuit brake
P01.29
current
Description
Output frequency
Running
Power off
Setting range: 0.0–3600.0s (valid when P01.21 is
1)
This function code sets the delay of the VFD's
wake-up-from-sleep after running command is
given, the VFD will start to run and output after the
time set by P01.23 elapses to realize brake
release.
Setting range: 0.0–600.0s
0: No voltage output
1: With voltage output
2: Output as per DC brake current of stop
0.0–60.0s
0.0–50.0s
0.0–50.0s
When the VFD starts in direct start mode
(P01.00=0), set P01.30 to a non-zero value to
- 213 -
t1=P01.22
t2=P01.23
t1
t2
Running
Power on
Function parameter list
Default
Modify
value
t
0.0s
0.0s
0
2.0s
0.1s
0.1s
0.0%