3 SPECIFICATIONS

3.4.2 Conversion enable/disable designation (buffer memory address 0: Un\G0)

3 - 15
(1) You can make setting to enable/disable temperature conversion on each channel.
(2) Specifying unused channels as "conversion disabled" prevents unnecessary
disconnection detection and also reduces sampling time.
(3) The Operation Condition Setting Request (Y9) must be turned on/off to make the
conversion enable/disable designation valid.
(4) At power-on or reset, the conversion enable/disable designation is set to 000F
(all channels disabled).
b15 b14 b13 b12 b11 b10
0
0
0
0
[Example]
b15 b14 b13 b12 b11 b10
0
0
0
0
Channels 1 and 2 are conversion enabled.
b9
b8
b7
0
0
0
0
0
b9
b8
b7
0
0
0
0
0
MELSEC-Q
b6
b5
b4
b3
b2
0
0
0
CH.4 CH.3 CH.2 CH.1
0: Conversion enabled
1: Conversion disabled
b6
b5
b4
b3
b2
0
0
0
1
1
H
b1
b0
b1
b0
0
0
3 - 15