3 SPECIFICATIONS
3.4.13 CH
temperature measurement value (32 bit) (buffer memory address 54 to 61:
Un\G54 to 61)
b31
0
b31
1
3.4.14 CH
scaling range upper/lower limit values (buffer memory address 62 to 77:
Un\G62 to 77)
3.4.15 CH
scaling width upper/lower limit values (buffer memory address 78 to 85: Un\G78
to 85)
3 - 22
(1) The "temperature-measuring resistance value" input from the platinum
temperature-measuring resistor is converted into a "temperature value" to detect a
temperature.
(2) The value of the measured temperature to the third decimal place is multiplied by
1000 and the result is stored into buffer memory in 32-bit signed binary. (All digits
to the right of the fourth decimal place are rounded down.)
(3) A negative temperature measurement value is displayed as two's complement.
(4) At power-on or reset, all channels are set to 0.
[Example 1] At the temperature measurement value of 123.025
b24b23
0
0
0
0
0
0
0
0
[Example 2] At the temperature measurement value of -123.025
b24b23
1
1
1
1
1
1
1
1
(1) Set the scaling range (0.001
channel.
(2) 0 is set at power-on or reset.
(3) The scaling range that may be set is -2147483648 to 2147483647.
(4) Scaling will not be made if the upper limit value and lower limit value are equal.
(5) The Operation Condition Setting Request (Y9) must be turned on/off to make the
setting valid.
(1) Set the scaling with on each channel.
(2) 0 is set at power-on or reset.
(3) The scaling range that may be set is -32768 to 32767.
(4) Set the upper limit value and lower limit value to 0 when scaling will not be made.
(5) The Operation Condition Setting Request (Y9) must be turned on/off to make the
setting valid.
b16b15
0
0
0
0
0
0
1
1
b16b15
1
1
1
1
1
1
0
1
increments) of the measured temperature on each
.....
b8 b7
1
1
0
0
0
0
0
1
.....
b8 b7
0
0
1
1
1
1
1
0
MELSEC-Q
123025 is stored.
b0
0
0
1
0
0
0
1
-123025 is stored.
b0
1
1
0
1
1
1
1
3 - 22