High Temperature Alarm (2.8.7.) - Siemens SITRANS LUT400 Operating Instructions Manual

Ultrasonic controllers
Hide thumbs Also See for SITRANS LUT400:
Table of Contents

Advertisement

Low Temperature Value ON (2.8.6.2.)
Sets the temperature value (defined in ° C) at which the Low Temperature Alarm will
activate.
Values
Low Temperature Value OFF (2.8.6.3.)
Sets the temperature value (defined in ° C) at which the Low Temperature Alarm will de-
activate.
Values
Assigned Relay (2.8.6.4.)
Determines which relay (if any) will be activated when the Low Temperature Alarm activates.
Options
Alarm State (2.8.6.5.)
Read only. Used to view the current state of the Low Temperature Alarm.
Options
9.2.8.7

High Temperature Alarm (2.8.7.)

Reported when process temperature is within a user-defined range (see High Temperature
Value ON (2.8.7.2.) (Page 203) or High Temperature Value OFF (2.8.7.3.) (Page 203)).
The temperature used for the alarm is the same temperature used for sound velocity
compensation (see Temperature Source (2.12.1.3.) (Page 218)).
202
Range: -273.0 to +273.0 °C (-459.0 to +523.0 °F)
Default: 0.0 °C
Range: -273.0 to +273.0 °C (-459.0 to +523.0 °F)
Default: 0.0 °C
*
ACTIVE
INACTIVE
Operating Instructions, 07/2019, A5E33329501-AC
NO RELAY
RELAY 1
RELAY 2
RELAY 3
SITRANS LUT400