Set The Common Parameters; Set Relays To Alternate Duty Assist (Ada); Set The On Setpoints - Siemens SITRANS LUT400 Operating Instructions Manual

Ultrasonic controllers
Hide thumbs Also See for SITRANS LUT400:
Table of Contents

Advertisement

7.7.2.1

Set the common parameters

Prerequisite: Substitute the details of your application in place of the sample values
provided. If you are bench testing the device, set your test values to be the same as the
sample values.
Parameter
Sensor Mode (2.1.2.) (Page 168)
Response Rate in Quick Start (Page 59)
Transducer (2.1.6.) (Page 170)
Units (2.1.1.) (Page 168)
Low Calibration Point (2.2.1.) (Page 171)
High Calibration Point (2.2.2.) (Page 172)
7.7.2.2

Set Relays to ALTERNATE DUTY ASSIST (ADA)

Parameter
Pump Control Mode (2.7.1.4.)
(Page 185) or Pump Control Mode
(2.7.1.5.) (Page 185)
7.7.2.3

Set the ON Setpoints

Parameter
ON Setpoint Pump 1
(2.7.1.6.) (Page 186)
ON Setpoint Pump 2
(2.7.1.8.) (Page 186)
Sample values denoted by asterisks in illustration on Setting a pump down (wet well) group
1)
(Page 104).
SITRANS LUT400
Operating Instructions, 07/2019, A5E33329501-AC
Sample Value
Level
Medium
XPS-10
M
1.8
0.4
Value
Description
ADA
Sets the control algorithm used to trip the pump
relay to ALTERNATE DUTY ASSIST. Multiple
pumps can run simultaneously.
Sample Value
Description
1
1.0 m*
Sets the level at which pump 1 turns on. The first
cycle will use this setpoint. Subsequent cycles
rotate the setpoint among the pumps. For exam-
ple: In cycle 1, pump 1 turns on at 1 m. In the
next cycle, pump 2 will turn on at 1 m.
1.1 m*
Sets the level at which pump 2 turns on.
General Operation
7.7 Pump Control
105