6.7
Testing the configuration
After programming the device, it is recommended that you test the device to ensure that it
performs to your specifications. This test can be run in simulation mode or by varying the
actual level in the application. The latter is preferred as it more accurately represents running
conditions. However, if it is not possible to do a physical test, a simulation will ensure that
control programming is correct. For further details, see Pump relay behaviour during
simulation (Page 154), and Application test (Page 157).
6.8
Application examples
In the examples that follow, substitute your own application details. If the examples do not
apply to your application, check the applicable parameter reference for the available options.
6.8.1
Level Application Example
①
②
③
④
⑤
⑥
⑦
⑧
⑨
Quick Start Parameter
Transducer
Operation
Temperature Source
Units
High Calibration Point
Low Calibration Point
Response Rate
see Fill Rate per Minute (2.3.1.) (Page 174)
1)
SITRANS LUT400
Operating Instructions, 07/2019, A5E33329501-AC
Distance 8.5 m
1.0 m
Sensor reference point
High calibration point
Space 7.5 m
15.0 m
Level 6.5 m
Low calibration point
Far range
Setting
Description
XPS-15
Transducer to be used with the LUT400.
LEVEL
Material level referenced from Low Cal. Point.
TS-3
Temperature source.
M
Sensor measurement units.
1.0
Process full level.
15.0
Process empty level.
SLOW
Sets Fill Rate
Commissioning
6.7 Testing the configuration
/ Empty Rate to 0.1 m/minute.
1
79