Siemens SITRANS LUT400 Operating Instructions Manual page 39

Ultrasonic controllers
Hide thumbs Also See for SITRANS LUT400:
Table of Contents

Advertisement

AC: 100-230 V AC 15%, 50/60 Hz, 36 VA (10W) DC: 10-32 V DC, 10W
Note
Make sure device is connected to a reliable ground.
1. To wire for power, strip the cable jacket for approximately 70 mm (2.75") from the end of
the cable, and thread the wires through the gland
2. Connect the wires to the terminals as shown: the polarity is identified below the terminal
block.
3. Ground the device according to local regulations.
If cable is routed through conduit, use only approved suitable-size hubs for waterproof
1)
applications.
Note
For AC power connections:
• The equipment must be protected by a 15 A fuse, or circuit breaker on all current-carrying
conductors in the building installation.
• A circuit breaker or switch in the building installation, marked as the disconnect switch,
must be in close proximity to the equipment and within easy reach of the operator, and must
disconnect all current-carrying conductors.
SITRANS LUT400
Operating Instructions, 07/2019, A5E33329501-AC
5.1 Connecting SITRANS LUT400
1
Connecting
37