Switch (Discrete Input) Alarm; Fail-Safe Fault Alarm - Siemens SITRANS LUT400 Operating Instructions Manual

Ultrasonic controllers
Hide thumbs Also See for SITRANS LUT400:
Table of Contents

Advertisement

General Operation
7.6 Alarms
Example: Setting a Low Temperature Alarm
To assign Relay 3 to a low level alarm that activates when the temperature falls below -10 °C
do the following:
1. Enable the Low Temperature Alarm (set Enable (2.8.6.1.) (Page 201) = Enabled)
2. Set Low Temperature Value ON (2.8.6.2.) (Page 202) = -10
3. Set Low Temperature Value OFF (2.8.6.3.) (Page 202) = -8
4. Set Assigned Relay (2.8.6.4.) (Page 202) to Relay 3.
Use Alarm State (2.8.6.5.) (Page 202) to view the current state of the Low Temperature
Alarm.
7.6.5

Switch (Discrete Input) Alarm

Activates an alarm when a discrete input is in a pre-defined state.
Example: Setting a Switch Alarm
To assign Relay 3 to a switch alarm that is activated when DI 1 turns ON do the following:
1. Enable the Switch (Discrete Input) Alarm (set Enable (2.8.3.1.) (Page 198) = Enabled)
2. Set the Discrete Input Number (2.8.3.2.) (Page 198) = 1
3. Set Discrete Input State (2.8.3.3.) (Page 199) to ON.
4. Set Assigned Relay (2.8.3.4.) (Page 199) to Relay 3.
Use Alarm State (2.8.3.5.) (Page 199) to view the current state of the Switch Alarm.
7.6.6

Fail-safe Fault Alarm

Activates an alarm when a fault that has caused a fail-safe condition is present.
Example: Setting a Fail-safe Fault Alarm
To assign a fail-safe fault alarm to Relay 3 do the following:
1. Enable the Fail-safe Fault Alarm (set Enable (2.8.8.1.) (Page 204) = Enabled)
2. Set Assigned Relay (2.8.8.2.) (Page 204) to Relay 3.
Use Alarm State (2.8.8.3.) (Page 204) to view the current state of the Fail-safe Alarm.
102
Operating Instructions, 07/2019, A5E33329501-AC
SITRANS LUT400

Advertisement

Table of Contents
loading

Table of Contents