General Operation
7.5 Volume
Example:
To configure volume for a vessel with a half-sphere bottom, set the following:
Parameter
Vessel Shape (2.6.1.)
(Page 180)
Maximum Volume
(2.6.3.) (Page 182)
Dimension A (2.6.4.)
(Page 182)
Note
• The default reading changes to a range from 0 to 100
• The process empty value is still measured to the bottom of the vessel (Low Calibration
Point (2.2.1.) (Page 171) plus any Far Range (2.2.5.) (Page 172)), not the top of
Dimension A.
96
Dimension A
Sample Value
HALF SPHERE
BOTTOM
100
1.3
Description
selects the correct vessel shape
sets maximum volume at 100 (defined in Vol-
ume Units (2.6.2.) (Page 181))
sets dimension A to 1.3 m
Operating Instructions, 07/2019, A5E33329501-AC
SITRANS LUT400