Reminder Activation (3.3.5.4.)
Note
To modify this parameter via SIMATIC PDM it must be accessed via the pull-down menu
Device – Maintenance.
Allows you to enable a maintenance reminder.
Values
1. First set the values in Reminder 1 before Service (Required) (3.3.5.5.)
(Page 254)/Reminder 2 before Service (Demanded) (3.3.5.6.) (Page 254).
2. Select the desired Reminder Activation option.
Reminder 1 before Service (Required) (3.3.5.5.)
If Time Next Service (3.3.5.3.) (Page 253) is equal to or less than this value, the device
generates a Maintenance Required reminder.
Values
1. Modify values as required.
2. Set Reminder Activation (3.3.5.4.) (Page 254) to the desired option.
Reminder 2 before Service (Demanded) (3.3.5.6.)
If Time Next Service (3.3.5.3.) (Page 253) is equal to or less than this value, the device
generates a Maintenance Demanded reminder.
Values
1. Modify values as required.
2. Set Reminder Activation (3.3.5.4.) (Page 254) to the desired option.
Maintenance Status (3.3.5.7.)
Indicates which level of maintenance reminder is active.
In PDM, open the menu View – Device Status, click on the Maintenance tab and check the
Service Schedule Status window.
254
*
TIMER OFF
ON NO LIMITS - no reminders checked
ON REMINDER 1 (MAINTENANCE REQUIRED) checked
ON REMINDER 1 AND 2 checked
ON REMINDER 2 (MAINTENANCE DEMANDED) checked
Range: 0.000 to 20.000 years
Default: 0.164 years (8 weeks)
Range: 0.000 to 20.000 years
Default: 0.019 years (1 week)
Operating Instructions, 07/2019, A5E33329501-AC