Burner Control with integrated Fuel / Air Ratio Control and Load Control for Forced-draft Burners Basic Documentation Valid for the following software versions: LMV51... : V01.90 Int. LC: V01.40 AZL51... : V01.70 Siemens Building Technologies CC1P7550en HVAC Products 29. 05. 2002...
Page 2
· Do not open, interfere with or modify the unit! · Siemens is not liable for any damage resulting from unauthorized interference! · In the event of blow n fuses, return the unit to Siemens! · Check electromagnetic emissions on an application-specific basis! To ensure the safety and reliability of the LMV51..., the following points must also be observed:...
Page 3
With proper oil burners, the magnetic clutch is not required. In that case, the long preignition time (from Phase 22) must be parameterized. · When using the PC software ACS450, the safety notes contained in the relevant Operating Instructions (CC1J7550) must be observed. 3/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 29.05.2002...
Page 4
The OEM assigns individual passwords to the parameter setting levels he can access. The default passwords used by Siemens must be changed by the OEM. These passwords are confidential and may only be given to persons authorized to access such parameter setting levels! ·...
Outputs valves-oil , type SI (V...) X8–02, X8–03, X7-01, X7-02 ... 31 Outputs valves -gas, type SI (V..., SV, PV) X9–01 ....... 31 Output oil pump / magnetic clutch, type No-SI X6–02 ......32 5/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products Contents 29.05.2002...
Page 6
Actuator speed outside normal operation ..........48 Operating position .................49 Modulating ..................49 Multistage operation ................49 4.1.2 Position check....................51 Dynamic safety time ratio control ............51 Outside the operating position ..............53 Operating position modulating ..............53 6/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products Contents 29.05.2002...
Page 8
Burner identification (burner ID) ............105 Makeup of burner ID................105 Languages ..................105 Real time clock and calendar ..............105 S / W changeover ................105 Backup.....................106 Batterietyp ..................106 Adjustment of contrast (display)............106 Shutdown function................106 8/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products Contents 29.05.2002...
Page 9
Fuses used in the basic unit LMV51........... 146 Dimensions ....................147 LMV51....................147 AZL51....................147 Addendum 1: List of error messages of LMV51... system..... 148 Addendum 2: Connection diagram............156 9/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products Contents 29.05.2002...
QRI... or ionization probes can be used for continuous operation, and photoresistive flame detectors type QRB... for intermittent operation. Basic diagram Example: Dual-fuel burner - Gas: Modulating - Oil: 2-stage 10/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 1 General 29.05.2002...
Page 11
The universal SQM4... actuators are driven by stepper motors and can be positioned with a high resolution. The characteristics and settings of the actuators are defined by the basic unit of the LMV51..11/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 1 General 29.05.2002...
Main group and basic design 7550s18E/0502 Burner control, microprocessor-based CAN bus system, dual- and single-fuel burner for continuous or intermittent operation, depending on the type of flame detector Gas valve proving 15/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 1 General 29.05.2002...
Power signal for safety loop OIL + GAS X3-04.3 Protective earth (PE) X3-04.4 Power supply neutral conductor (N) F 6,3 AT X3-04.5 Power supply live conductor (L) 16/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 1 General 29.05.2002...
Page 17
AGG5.2xx X10-03.1 Ionization probe (ION) Neutral conductor X10-01.4 FLAME Power signal LINE X10-01.3 transformer X10-01.2 AC power signal G0 SEK I 12VAC AC power signal G X10-01.1 17/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 1 General 29.05.2002...
® Phase change in Phase 40 Direct heavy oil start = OFF at the end of Phase 38 ® Repetition (max. 3 times in total) Multistage operation 7550f01cE/0200 22/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 2 Fuel train applications (examples) 29.05.2002...
Page 23
Oil trains LOgp and HOgp are designed for ignition with a gas pilot. They must always be combined with special gas train Gp2 for operation with a dual-fuel burner. With Gp2 permitted from HW 01.C0 and SW V01.40 23/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 2 Fuel train applications (examples)
® Phase change in Phase 40 Direct heavy oil start = OFF at the end of Phase 44 Operation ® Repetition (max. 3 times in total) Two stage operation 25/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 2 Fuel train applications (examples) 29.05.2002...
Landis & Staefa X10-02 / 4 Made in Germany X10-02 / 2 brown 7719a01E/0502 0...10 V Ri > 10 MW For detailed information, refer to Data Sheet 7719. 26/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 3 Burner control 29.05.2002...
Page 27
It should also be noted that, for physical reasons, there is no linear relationship between the display and the detector signal values. This is especially obvious with ionization current supervision. For more detailed information, refer to Data Sheet 7714. 27/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 3 Burner control...
If none of the 2 inputs is active, the burner’s output is maintained at a constant level. The shortest permissible positioning step is about 100 ms. (Parameter text) in Italics = text displayed on the AZL51… 28/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 3 Burner control 29.05.2002...
There is a delayed reaction to loss of gas pressure during «ts1» and «ts2» to prevent shutdown caused by pressure shocks when the valves open. Parameter: PressReacTme 29/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 3 Burner control...
The input has been designed for the connection of an air pressure switch for flue gas recirculation (only from LMV52...). c) Parameter: Config_FGR-PS/FCC (deactivated) The function of the input can be deactivated. 30/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 3 Burner control 29.05.2002...
These outputs are used for connecting the gas valves in accordance with the selected type SI fuel train. ® Fuel trains, ® sequence diagrams. (V..., SV, PV) Parameter: FuelTrainGas (DirectIgniG / Pilot Gp1 / Pilot Gp2) X9–01 31/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 3 Burner control 29.05.2002...
This valve is required when parameterizing NormDirectStart (NormalStart / DirectStart) ® direct start for testing the air pressure switch if ContinuousPurge is parameterized (activated) ® continuous purging. 32/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 3 Burner control...
Then, the gas train is filled by opening the gas valve t82 Fill on the gas network side. After shutting the gas valve, the gas pressure may not t83 Pressure test drop below a certain level. 33/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 3 Burner control 29.05.2002...
(Gp1) t Test in s Test time Examples Refer to chapter «Commissioning instructions for LMV51... system» / gas valve proving / leakage test. 34/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 3 Burner control 29.05.2002...
If this reaction is not desired, it is possible to feed power to the reset button from the alarm output, thus obtaining the same reaction as described in 1. above. 35/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 3 Burner control 29.05.2002...
Phase 79 to Phase 24 without switching the fan off, so that the startup sequence will be accelerated. But this would suppress checking the air pressure switch’s OFF position in standby. 37/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 3 Burner control 29.05.2002...
If ® direct start has been parameterized, fuel changeover can also take place on shutdown in Phase 76. The fan will not be switched off. 38/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 3 Burner control 29.05.2002...
Fuel valve V3 Oil pump / magnetic clutch 90° 0° Required position 90° 0° Required position 7550f13E/0601 Program «Direct gas ignition» (also refer to «Fuel trains») 39/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 3 Burner control 29.05.2002...
Oil pump / magnetic clutch 90° 0° Required position 90° 0° Required position 7550f18E/0601 Program «Light oil with gas pilot ignition (LOgp)» (also refer to «Fuel trains») 44/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 3 Burner control 29.05.2002...
Oil pump / magnetic clutch 90° 0° Required position 90° 0° Required position 7550f19E/0601 Program «Heavy oil with gas pilot ignition (HOgp)» (also refer to «Fuel trains») 45/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 3 Burner control 29.05.2002...
Stop to Ph-max time -> 01 Safety Limit Thermostat Continuous purging: Checking for on in 10 and 12, Safety Relay Temperature Limiter Stop to Ph-max time -> 01 46/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 3 Burner control 29.05.2002...
Ignition takes place only when the required position is reached. The ignition position can be adjusted for all actuators, depending on the type of fuel. Parameter: IgnitionPosAir Parameter: IgnitionPosGas or parameter IgnitionPosOil Parameter: IgnitionPosAux 47/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 4 Fuel / air ratio control (FARC) 29.05.2002...
Outside normal operation, all actuators travel at that speed. Note When parameterizing the operating ramp, the speed of the slowest actuator must be taken into consideration! 48/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 4 Fuel / air ratio control (FARC)
SetPointStage1 Parameter: StartPointStage2 Parameter: OffPointStage2 Parameter: SetPointStage2 Parameter: StartPointStage3 Parameter: OffPointStage3 Parameter: SetPointStage3 Pos. 7550d02E Load S2on S2off Multistage operation (here: 2-stage) 49/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 4 Fuel / air ratio control (FARC) 29.05.2002...
Page 50
Then, the ratio position of «operating point S1» will be approached again. The procedure is analogous when switching from stage 2 to stage 3 and back again. 50/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 4 Fuel / air ratio control (FARC) 29.05.2002...
2° in no more than 3 seconds. Otherwise, safety shutdown occurs. Also, the neutral band must be reached within 8 seconds after starting the change in position. 51/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 4 Fuel / air ratio control (FARC)
Page 52
Pos. [°] Required position -0,3 Alarm Actual position 7550d18E/0502 < 5 s Locking on change of load (approach < 2° > 0.3°) 52/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 4 Fuel / air ratio control (FARC) 29.05.2002...
If the auxiliary actuator is not required, it must be deactivated. This can be selected auxiliary actuator separately for both types of fuel. Parameter: AuxActuator (deactivated / activated) 54/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 4 Fuel / air ratio control (FARC) 29.05.2002...
20 % above the value for TmeNoFlame parameterized. Curve adjustment Refer to chapter «Displays and settings» / special function curve adjustment FARC. 55/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 4 Fuel / air ratio control (FARC)
Operating mode 1 External load controller. (extLC) In this operating mode, an external load controller (e.g. Siemens RWF40) is used. The internal control algorithm is not active. The internal temperature limiter function can be activated. The external load controller must have 3 contact outputs which - as shown below - must be connected to the LMV51...
PID standard values for the following applications: Parameter: Standardparam (very fast / fast / normal / slow / very slow) 62/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 5 Temperature or pressure controller (internal load controller LC)
The new control parameters appear on the AZL... and are valid from now on. Note Refer to chapter «Displays and settings» / special function adaption LC 63/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 5 Temperature or pressure controller (internal load controller LC)
XP too great 7550d22/0501 7550d21/0501 TN and TV too small TN and TV too great 7550d23/0501 7550d24/0501 Optimum setting 7550d25/0501 64/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 5 Temperature or pressure controller (internal load controller LC) 29.05.2002...
Range of a small number of large steps of the controlling element In this range, small steps of the controlling element are suppressed since they would not yet have any major impact. 65/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 5 Temperature or pressure controller (internal load controller LC) 29.05.2002...
In that case, stage 1 will already be switched off when threshold W+SD_Stage3Off is reached (low-fire operation). Setpoint Actual value SD_Stage1Off SD_Stage2Off SD_Stage3Off SD_Stage1On R=ON Stage1 Stage 2 Stage 3 7550f09E/0502 66/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 5 Temperature or pressure controller (internal load controller LC) 29.05.2002...
150 °C or 302 °F End of measuring range: or (can be parameterized) 400 °C or 752 °F Parameter: Inp1/4/MaxValue 67/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 5 Temperature or pressure controller (internal load controller LC) 29.05.2002...
Pt1000 / LG-Ni 1000 are small compared to the sensor's resistance. The TL function is active. The sensors to be used are the Siemens types QAE22.5A and QAE21.1. Start of measuring range: 0 °C or 32 °F 150 °C or 302 °F...
If, in addition, a temperature sensor Pt100 (and / or Pt1000, LG-Ni1000 sensor) is connected, it is also possible to use the internal temperature limiter function with the external predefined load. 69/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 5 Temperature or pressure controller (internal load controller LC) 29.05.2002...
LC_OptgMode (intLC o.DDC / extLC o.DDC) An external predefined setpoint via e-bus exists with «intLC via BMS». An external predefined load via e-bus exists with «extLC via BMS». 70/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 5 Temperature or pressure controller (internal load controller LC)
Instant temperature change of test medium to determine the time constant Temperature of test medium Output signal of temperature sensor Time constant 71/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 5 Temperature or pressure controller (internal load controller LC)
Manipulated variable increased Change to control by output step old ON. variable increased by Burner will be output step switched on 7550d04E/0202 72/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 5 Temperature or pressure controller (internal load controller LC) 29.05.2002...
Burner OFF Part load Nominal load I (mA) Output, multistage Burner OFF Stage 1 Stage 2 Stage 3 I (mA) 73/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 5 Temperature or pressure controller (internal load controller LC) 29.05.2002...
Display and operating unit AZL51... Display and operating unit AZL51... 75/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 6 Display and operating unit AZL51... 29.05.2002...
Port for BMS via external e-bus interface Port for the LMV51… basic unit Note COM1 and COM2 cannot be active at the same time! 76/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 6 Display and operating unit AZL51...
8-pin Western 25-pin SUB-D connector 7550t02E/0502 Connecting cable AZL COM1 Cable PC COM to the PC 9-pin connector 9-pin socket 7550t01E/0502 77/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 6 Display and operating unit AZL51... 29.05.2002...
Note The CAN connection to the basic unit can simultaneously be combined with only one of the 2 ports, either «Interface PC» or «Gateway BMS». 78/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 6 Display and operating unit AZL51...
· Final temperature or pressure setpoint · Contents of lockout and error storages · Existence inquiry e-bus infrastructure · Querying supported commands · Error message 79/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 6 Display and operating unit AZL51... 29.05.2002...
Identification Query of the supported commands Existence inquiry Sign of life Readout of LMV error storage (Siemens-specific) Readout of LMV lockout storage (Siemens-specific) Error message For details, refer to e-bus specification, Application Layer OSI7 of User Club eBUS e. V.
( P h a s e 2 4 ) S T A R T U P I V ( P h a s e s 3 0 . . . 3 4 ) 82/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 6 Display and operating unit AZL51...
Page 83
( P h a s e 6 0 ) ° ° O P E R A T I O N I I ( P h a s e 6 2 ) 83/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 6 Display and operating unit AZL51... 29.05.2002...
Page 84
( P h a s e 7 9 ) V A L V E P R O V I N G ( P h a s e s 8 0 . . . 8 3 ) 84/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 6 Display and operating unit AZL51...
In contrast to the lockout history, the error history contains the errors of all error classes and not only the lockouts. If an error occurs, the display alternates at 5-second intervals. Example: Safety loop open 85/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 6 Display and operating unit AZL51...
Page 86
In the event of safety shutdown, the display alternates at 5-second intervals. Example: Immediate display of warnings In the event of warnings, the display alternates at 5-second intervals. 86/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 6 Display and operating unit AZL51...
Page 87
Lockout and error messages Example: Immediate display of start preventions (cont‘d) In the event of start preventions, the display alternates at 5-second intervals. 87/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 6 Display and operating unit AZL51... 29.05.2002...
Selection of the associated main menu item: The main menu item «Parameterization & Display» is called up and selected as described above: & = flashing cursor 88/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 6 Display and operating unit AZL51... 29.05.2002...
When the last character of the password is reached, the entry is to be confirmed by pressing ENTER. · The passwords are linked to the access levels (Service, OEM, Siemens). This means that the parameters available for editing are only those associated with the access level ·...
Page 90
- 0...12.6 s resolution 0.2 s - 13...63 s resolution 1 s - 70...630 s resolution 10 s - 11...63 min resolution 1 min 90/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 6 Display and operating unit AZL51... 29.05.2002...
This procedure can be repeated for other actuators used by the system, but the AZL51… does not allow double assignments. In that case, a display tells the user that an appropriate actuator is already used by the system. 91/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 6 Display and operating unit AZL51...
4 pulses Þ auxiliary actuator After each blink cycle, there is a pause of 1.2 seconds. Example of an actuator for gas 7550d12E Time 92/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 6 Display and operating unit AZL51... 29.05.2002...
2. Ratio control is operated manually until the value reached shall be stored as a new point. A more detailed description of both approaches is given below: 93/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 6 Display and operating unit AZL51...
Page 94
Select the required breakpoint, then continue with ENTER ß Here, the pointer position can change between «change?» and «delete?». To edit the point, «change?» must be selected here. 94/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 6 Display and operating unit AZL51...
Page 95
(during the storage process, no buttons will be evaluated. To indicate this, a symbol appears on the display). The changes can be rejected by pressing ESC. 95/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 6 Display and operating unit AZL51...
Page 96
The procedure is the following: After leaving menu item «CurveParams», position the pointer on «Man» when reaching the menu. - Pointer positioned on «Man»: 96/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 6 Display and operating unit AZL51... 29.05.2002...
Page 97
To readjust the ignition positions after the burner has ignited: «ProgramStop» to «Stop_Ph44», or «Stop_Ph52» for pilot ignition after the pilot flame has been shut down. Then, on «ProgramStop», set to «Stop_Ph72». 97/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 6 Display and operating unit AZL51...
Page 98
A point can be saved at every intermediate point. Then, the load / position graph will look as follows: 90° Pos. FUEL 0° 100 % 7550d08E Load Change of load / position with two points 98/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 6 Display and operating unit AZL51... 29.05.2002...
Page 99
Now, the postpurge positions on menu «Special positions» can be set. Then, on «Program Stop», set to «deactivated». The system continues the shutdown sequence and stops in phase «Standby 12». 99/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 6 Display and operating unit AZL51...
Page 100
S e t t i n g m o d u l a t i n g r a t i o c o n t r o l Refer to selection menu «S e t t i n g s G a s » 100/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 6 Display and operating unit AZL51...
Page 101
This has no impact on the system, even if «Followed» has been selected. Example: Not followed. If «Followed» is selected, the parameters are set as follows: 101/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 6 Display and operating unit AZL51...
Page 102
Switch-off point stage 3 stage 3 Operating point stage 3 Approach of stage 3 Fine adjustment of stage 3 System response when a point is selected 102/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 6 Display and operating unit AZL51... 29.05.2002...
Adaption starts after pressing ENTER whereupon the following text appears: ° Depending on the adaption step, the following displays appears, alternating with the display shown above: ° 103/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 6 Display and operating unit AZL51... 29.05.2002...
Page 104
If a running adaption is manually canceled by pressing ESC, the following text will also appear: The system changes to «Normal operation». In that case, the previous PID parameters will be maintained. 104/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 6 Display and operating unit AZL51...
So, it is possible to have data transmission between the basic unit and the AZL51… of one plant (burner IDs are identical) and between an AZL51… and a new basic unit (burner ID «as supplied» by Siemens). Data transmission between AZL51… and basic units of different plants (burner IDs not identical) is not possible (no «cloning»!).
Shutdown function Lockout of the basic unit can be triggered by simultaneously pressing ENTER and ESC. Lockout will be stored in the AZL51..106/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 6 Display and operating unit AZL51...
Definition of access rights. Parameters can be set by: User : Plant operator Service : Heating engineer OEM : Boiler / burner manufacturer Basic parameter setting Factory-set parameter 107/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 6 Display and operating unit AZL51... 29.05.2002...
Page 108
Total number of startups, start counter (read only) 0..999999 h User LockoutCounter Total number of lockouts that occurred (read only) 0..65535 User BurnerID Identification of burner 4..15 characters User invalid 108/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 6 Display and operating unit AZL51... 29.05.2002...
Page 109
Normal / direct start in the event of heat demand in NormalStart NormalStart phase 78 DirectStart IgnOilPumpStart Switch-on time of ignition and oil pump on in Ph38 on in Ph38 on in Ph22 109/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 6 Display and operating unit AZL51... 29.05.2002...
Page 110
Configuration of input on PM-VP or CPI PS-VP PS-VP VP_EvacTme Proving test evacuation time 0.2..3 s VP_TmeAtmPress Proving test test time atmospheric pressure MinT_VP_Atm Press..63 s 10 s 110/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 6 Display and operating unit AZL51... 29.05.2002...
Page 111
S etting the postpurge positions for firing on oil Service P ostpurgePos P ostpurgeP osOil P ostpurge position of fuel dam per (oil) 0..90° Service 0° 111/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 6 Display and operating unit AZL51... 29.05.2002...
Page 112
0..100 bar S etpointW 2 Internal setpoint W 1, in degrees Celsius 0..2000 °C User Internal setpoint W 1, in bar 0..100 bar 112/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 6 Display and operating unit AZL51... 29.05.2002...
Page 113
Inp2PresMaxValue End of pressure m easurem ent range for input 2 (4..20 m A, 0..99.9 bar Service 2 bar 0..10 V, 2..10 V) 113/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 6 Display and operating unit AZL51... 29.05.2002...
Page 114
3 OilActuator Direction of rotation of the respective actuator Standard Standard Reversed 4 AuxActuator Direction of rotation of the respective actuator Standard Standard Reversed 114/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 6 Display and operating unit AZL51... 29.05.2002...
Page 115
End of measurement range for sensor at inputs 1 and 4 150 °C / 302 °F Service 150 °C / 302 °F 400 °C / 752 °F 115/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 6 Display and operating unit AZL51... 29.05.2002...
Page 116
Cancelling the last access right obtained via password Service SafetyCheckFunct Safety check function User LossFlameTest Loss of flame test User SLT Test Safety limit thermostat test deactivated User deactivated activated 116/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 6 Display and operating unit AZL51... 29.05.2002...
ValveProving ValveProvingType Selection of gas valve proving: No VP, VP startup, VP shutdown or VP stup/shd ( ® «Gas valve proving system») 117/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 7 Commissioning instructions for the LMV51... system 29.05.2002...
Page 118
Menu level 2 Menu level 3 Menu level 4 Menu level 5 Menu level 6 Params & Display RatioControl GasSettings AuxActuator OilSettings AuxActuator 118/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 7 Commissioning instructions for the LMV51... system 29.05.2002...
Page 119
Inp3Config_C/V Inp3MinSetpoint Inp3MaxSetpoint On the configuration level of the LC, select the required type of sensor. Then, define the sensor’s measuring range. 119/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 7 Commissioning instructions for the LMV51... system 29.05.2002...
Menu level 6 ManualOperation Autom/Manual/Off If startup shall be watched, press simultaneously selection buttons «<» and «>» to switch the display to «Normal operation». 120/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 7 Commissioning instructions for the LMV51... system 29.05.2002...
Page 121
· Now, select the second curvepoint. The settings of the previous curvepoint will be adopted on a preliminary basis · Store the second curvepoint like the first one 121/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 7 Commissioning instructions for the LMV51... system...
Page 122
Menu level 2 Menu level 3 Menu level 4 Menu level 5 Menu level 6 Params & Display RatioControl GasSettings CurveParams Point Manual 122/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 7 Commissioning instructions for the LMV51... system 29.05.2002...
Menu level 2 Menu level 3 Menu level 4 Menu level 5 Menu level 6 Params & Display RatioControl OilSettings CurveParams Operation Mode 123/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 7 Commissioning instructions for the LMV51... system 29.05.2002...
Page 124
ManualOperation Autom/Manual/Off If startup shall be watched, the display can be changed to «Normal operation» by pressing simultaneously selection buttons «<» and «>». 124/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 7 Commissioning instructions for the LMV51... system...
Page 125
Menu level 4 Menu level 5 Menu level 6 Params & Display RatioControl OilSettings CurveParams Curve Settings Actuator Positions followed not followed 125/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 7 Commissioning instructions for the LMV51... system 29.05.2002...
Page 126
Select «Autom/Manual/Off» and choose «BurnerOff». Menu level 1 Menu level 2 Menu level 3 Menu level 4 Menu level 5 Menu level 6 ManualOperation Autom/Manual/Off 126/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 7 Commissioning instructions for the LMV51... system 29.05.2002...
Volume between the valves (test volume) including valve volume and pilot path (Gp1) if present t Test in s Test time 127/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 7 Commissioning instructions for the LMV51... system 29.05.2002...
Page 128
= 3 l 1013 mbar • 4 s t Test = 4 s Result: The detected leakage rate is 40 l / h 128/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 7 Commissioning instructions for the LMV51... system 29.05.2002...
Menu level 2 Menu level 3 Menu level 4 Menu level 5 Menu level 6 Params & Display LoadController Configuration Inp1/4/MaxValue 150°C/302°F 400°C/752°F 129/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 7 Commissioning instructions for the LMV51... system 29.05.2002...
Menu level 2 Menu level 3 Menu level 4 Menu level 5 Menu level 6 Params & Display LoadController Adaption StartAdaption AdaptionLoad 130/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 7 Commissioning instructions for the LMV51... system 29.05.2002...
Page 131
+10 % ( = 7 K) Controller loop open (Off) 70 + 3.5 = 73.5 °C Controller loop closed (On) 70 - 7 = 63 °C 131/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 7 Commissioning instructions for the LMV51... system 29.05.2002...
Page 132
StageStep_Mod 10 % of setpoint Max. time modulating per step MaxTmeMod 5 minutes Shock protection deactivation level ThresholdOff 80 % of setpoint 132/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 7 Commissioning instructions for the LMV51... system 29.05.2002...
Page 133
Menu level 4 Menu level 5 Menu level 6 Params & Display LoadController ColdStart ColdStartOn ThresholdOn StageLoad StageStep_Mod StageStep_Stage MaxTmeMod MaxTmeStage ThresholdOff 133/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 7 Commissioning instructions for the LMV51... system 29.05.2002...
· To isolate the unit from the mains supply, a multipolar switch must be used. · For wiring the bus users, only the cables specified by Siemens may be used! · The electrical contacts used by the external signal sources (DWmin, max, LC, etc.) must be gold-plated silver contacts!
230 V LMV51... basic unit Power trafo 1 7550a03E/0202 AGG5.2xx X3-04 Note on example 1 Total length of bus cable £ 100 m 137/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 9 Mounting, electrical installation and service 29.05.2002...
Page 138
(Type1) to all the other actuators. The fuses required for transformer 1 are accommodated in the LMV51... basic unit. For transformer 2, these 3 fuses must be located close to the transformer. 138/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 9 Mounting, electrical installation and service 29.05.2002...
(2 x SQM45.xxx) gives a maximum cable length of 33.4 m between the transformer and the group of actuators. The minimumcross-sectional area is 0.33 mm 139/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 9 Mounting, electrical installation and service...
AGG5.630 / 631 (cable type 2) LMV51... « AZL51… Silver-grey RAL 7001 0.50 mm 0.50 mm 0.50 mm Shield 2 x 0.25 mm Drilled pair 140/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 9 Mounting, electrical installation and service 29.05.2002...
/ PC adapter Fa. Karl Dungs GmbH & Co. part no. 230 437 Steuer- und Regeltechnik Postfach 1229 D-73602 Schorndorf User Club eBUS e.V. www.eBUS.de 141/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 9 Mounting, electrical installation and service 29.05.2002...
It must be made certain that all safety notes and the notes on mounting, electrical installation and service according to the above mentioned Data Sheets are complied with. 143/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 10 Duties of the authorized inspector...
· Unit input current* (safety loop) max. 5 A * Total contact current resulting from: Fan motor contactor Ignition transformer Valves Oil pump / magnetic clutch 145/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 11 Technical data 29.05.2002...
Cable insulation must satisfy the requirements of the relevant temperature and environmental conditions. The CAN (bus) cables have been specified by Siemens and can be ordered as accessory items. Other types of cables may not be used. Otherwise, the EMC characteristics of the LMV51...
In case of departure from the valid range when com m issioning the unit for the first tim e: Readjust to ensure valid value range If fault occurs after operation has been correct: Replace the faulty basic unit 148/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 13 Addendum 1: List of error messages of LMV51...
Page 149
149/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 13 Addendum 1: List of error messages of LMV51...
Page 150
Fault in connection with plausibility check. For cause of fault, refer to the diagnostic code No Fuel Train defined No defined fuel train param eterized 150/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 13 Addendum 1: List of error messages of LMV51... system...
Page 151
If resetting does not solve the problem : Restore the param eters of the AZL51... Otherwise, replace the basic unit 151/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 13 Addendum 1: List of error messages of LMV51... system...
Page 152
Fault Feedback Aux Actuator auxiliary actuator when checking the actuator's If fault occurs perm anently: Replace the faulty auxiliary actuator feedback signal 152/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 13 Addendum 1: List of error messages of LMV51... system...
Page 153
Adaption invalid TU greater than identification time Adaption invailid Invalid TV identified Timeout with Adaption Timeout during observation time 153/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 13 Addendum 1: List of error messages of LMV51... system 29.05.2002...
Page 154
CAN warning level No valid Parameter Backup Fault when copying a parameter page Reset the unit; repeat backup restore, if required 154/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 13 Addendum 1: List of error messages of LMV51... system...
Page 155
6 / auxiliary actuator 7 / not used If fault occurs sporadically: Improve EMC If fault occurs permanently: Replace the faulty basic unit 155/157 Siemens Building Technologies Basic Documentation LMV51... CC1P7550en HVAC Products 13 Addendum 1: List of error messages of LMV51... system...