Note
• When Transducer (2.1.6.) is set to NO TRANSDUCER, the LOE fault will display
immediately.
• An Echo Profile (3.2.1.) (Page 241) cannot be requested from LUI when Transducer
(2.1.6.) is set to NO TRANSDUCER. The local push button will not operate.
9.2.1.7

Frequency (2.1.7.)

Adjust the shot transmit pulse frequency (in kHz).
Values
9.2.1.8

Long Shot Duration (2.1.8.)

Adjust the duration of the long shot transmit pulse (in µs).
Values
9.2.1.9

Short Shot Duration (2.1.9.)

Adjust the duration of the short shot transmit pulse (in µs).
Values
9.2.2

Calibration (2.2.)

9.2.2.1

Low Calibration Point (2.2.1.)

Distance from sensor reference point
(Page 168).
Values
The point from which level measurement is referenced (see Sensor Mode (2.1.2.)
1)
(Page 168) for illustration).
SITRANS LUT400
Operating Instructions, 07/2019, A5E33329501-AC
Range: 10.000 to 52.000
Default: Depends on transducer selected in Transducer (2.1.6.) (Page 170).
Range: 100.000 to 2000.000
Default: Depends on transducer selected in Transducer (2.1.6.) (Page 170).
Range: 100.000 to 2000.000
Default: Depends on transducer selected in Transducer (2.1.6.) (Page 170).
1
to Low Calibration Point defined in Units (2.1.1.)
Range: 0.000 to 60.000
Default: 60.000
171