[Pr. PA13.1_Pulse train logic selection]
Initial value
0h
0: Positive logic
1: Negative logic
Match the logic of the command pulse train received from the connected controller.
Refer to the following for setting values.
Page 20 [Pr. PA13.0_Command input pulse train form selection]
[Pr. PA13.2_Command input pulse train filter selection]
Initial value
1h
Selecting the appropriate filter for the command pulse frequency can increase noise tolerance.
0: Command input pulse train is 4 Mpulses/s or less
1: Command input pulse train is 1 Mpulse/s or less
2: Command input pulse train is 500 kpulses/s or less
3: Command input pulse train is 200 kpulses/s or less
"1" can be set for commands up to 1 Mpulse/s. When inputting commands exceeding 1 Mpulse/s and up to 4 Mpulses/s, set
"0".
To prevent the following malfunctions, set a correct value in accordance with the command pulse frequency.
Setting a value higher than the actual command value will decrease noise tolerance.
Setting a value lower than the actual command will cause a position mismatch.
Setting range
Refer to the text
Setting range
Refer to the text
1.2 Basic setting servo parameters group ([Pr. PA_ _ ])
Ver.
A0
Ver.
A0
1 SERVO PARAMETER DETAILS