For the assembly or disassembly of modules, please refer
to the chapter „Connection and assembly of internal modu-
les" plus all warning notices!
NOTE!
The service button on the front panel must be pressed to
log on and off circuit changeovers.
Control and change of external modules
To assemble or disassemble a module, proceed as descri-
bed ander „Connection and assembly of external modu-
les" . Please note here:
For modules with address switches, set the address pro-
vided for the module. Avoid multiple assignment, as this
will lead to malfunctions.
In order for replaced external modules to function correct-
ly ander the control, they must have been identified, acti-
vated and parameterised via the control software.
A service pin is located on the module which can be used
during initial commissioning or for test and inspection
purposes. This pin is used to display the addresses and
properties of the respective module directly on the touch
display of the HMI via the control software.
Mounting- and Operating Instruction CEAG DualGuard-S 40071860347 January 2020 www.ceag.de
14 Check the fuses of the mains or battery power supply.

15 Switching on the system

Switch on the mains power supply of the switch cabinet
and its substations via the switch-disconnectors.
Use the switch-disconnectors to switch on the battery
power supply of the switch cabinet and its US-S subsys-
tems.
After switching on the system, the colour touch display
shows the current system status. All connected escape
sign and safety lights are switched on and the system
automatically switches to battery operation if its power
supply fails.

16 Device Configuration

After switching on the system there are the following pos-
sibilities to configure the system.
1) Data download via PC software and USB stick (recom-
mended)
2) Web configuration (only possible if the systems have
Internet access)
3) VisionGuard configuration (only possible from VisionGuard
version xxx)
4) Manually via HMI (recommended for smaller installati-
ons without complex configuration or for smaller modi-
fications)
IMPORTANT NOTE!
The systems and luminaires are supplied ex works in such
a way that the emergency lighting function is guaranteed
even without customer-specific configuration.
Configuration of the national language
By touching the icon
the desired language can be set.