Communication extension card
series VFD SWs.
Bit
0–7
8
Bus voltage established
9–10
Motor group feedback
11
Motor type feedback
12
Overload pre-alarm feedback
13–14
Run/Stop mode
15
Heartbeat feedback
Actual value (ACT): The second to twelfth words in a PZD task packet are the main actual
values. The main actual frequency values are provided by the main actual value signal source.
Function
code
P16.43
Transmitted PZD2 0: Invalid
P16.44
Transmitted PZD3
P16.45
Transmitted PZD4
P16.46
Transmitted PZD5
P16.47
Transmitted PZD6
P16.48
Transmitted PZD7
P16.49
Transmitted PZD8
P16.50
Transmitted PZD9
P16.51
Transmitted PZD10
P16.52
Transmitted PZD11
Table 4-7 Goodrive350 series VFD SWs
Name
Running state
Table 4-8 Actual state values of Goodrive350 series VFD
Word
Value
1
2
3
4
5
1
0
0
1
1
0
1
0
0
1
2
3
1
0
Value range
1: Running frequency (×100, Hz)
2: Set frequency (×100, Hz)
3: Bus voltage (×10, V)
4: Output voltage (×1, V)
5: Output current (×10, A)
6: Actual output torque (×10, %)
7: Actual output power (×10, %)
8: Rotating speed of the running (×1,
RPM)
-52-
PROFINET communication card
Description
In forward running
In reverse running
Stopped
Faulty
POFF
Ready to run
Not ready to run
Motor 1
Motor 2
Synchronous motor
Asynchronous motor
Overload pre-alarm generated
No overload pre-alarm generated
Keypad-based control
Terminal-based control
Communication-based control
Reserved
Heartbeat feedback
No heartbeat feedback
Default
value
0
0
0
0
0
0
0
0
0
0