WAGO-I/O-SYSTEM 750
750-632 Proportional Valve Module
Table 87: Parameters, Table 33 (DI1)
Register Name,
11.4.1.5
Table 40 (Additional Module Parameters
Table 88: Parameter, Table 32 (Module Monitoring)
Register Name,
0
Manual
Version 1.3.0, valid from FW/HW-Version 01/01
Bits
Type
Explanation
Bits
Type
Explanation
PWR_EN_USE
0
_STOPRAMP,
UINT16
Value/Range
Description
(Default)
3
HOLD Valve 1
Maintains current setpoint
value.
Note:
This function is state-controlled:
•
If the input is activated, the
"HOLD" function is also
activated. The setpoint
value cannot be
approached.
•
If the input is deactivated,
the "HOLD" function is
also deactivated. The
current setpoint value is
approached.
4
Jog + Valve 1
OR function using control bit 7
for Valve 1
5
Jog - Valve 1
OR function using control bit 6
for Valve 1
6
Jog + Valve 2
OR function using control bit 7
for Valve 2
7
Jog - Valve 2
OR function using control bit 6
for Valve 2
8 ... 255
(reserved)
Value/Range
Description
(Default)
0 ... 1
Use stop ramp to disable the
(Default: 0)
output stages. Use stop ramp to
approach the substitute value.
Appendix
121