66
Process Image
Table 47: Locking the Bits M_UP and M_DOWN
JOGPOS_ACK
0
0
1
1
Table 48: Status Byte S1
Bit 7
JOGPOS_
ACK
Key
JOGPOS_
ACK
JOGNEG_ACK
DITHER_ST
DI1
DI2
ON_TARGET
READY
* Applies to software version 03 or higher
Table 49: Status Byte S2
Bit 7
JOGPOS_
ACK
Key
JOGPOS_
ACK
JOGNEG_ACK
DITHER_ST
Bit 4 ... Bit 2
ON_TARGET
READY
* Applies to software version 03 or higher
JOGNEG_ACK
0
1
0
1
Bit 6
Bit 5
JOGNEG_
DITHER_S
ACK
T
JOGPOS_ACK
Acknowledgment bit for JOGPOS
JOGNEG_ACK
Acknowledgment bit for JOGNEG
DITHER_ST
Status of dither function
0:
Dithering OFF
1:
Dithering ON
Function for the configuration of 1 valve:
V1_Status1
V1_Status1.DI1
Status digital input DI1:
0: Uin < 5 V
1: Uin > 15 V
Function for the configuration of 1 valve:
V1_Status1.DI2
Status digital input DI2
0: Uin < 5 V
1: Uin > 15 V
0: Actual value is not in the range "Setpoint value +/- ON_TARGET_WINDOW".
1: Actual value is in the range "Setpoint value +/- ON_TARGET_WINDOW".*
0: Output stage deactivated, e.g. due to an error
1: Output stage activated
Bit 6
Bit 5
JOGNEG_
DITHER_S
ACK
T
JOGPOS_ACK
Acknowledgment bit for JOGPOS
JOGNEG_ACK
Acknowledgment bit for JOGNEG
DITHER_ST
Status of dither function
0:
Dithering OFF
1:
Dithering ON
0: reserved
0: Actual value is not in the range "Setpoint value +/- ON_TARGET_WINDOW".
1: Actual value is in the range "Setpoint value +/- ON_TARGET_WINDOW".*
0: Output stage deactivated, e.g. due to an error
1: Output stage activated
750-632 Proportional Valve Module
Status Byte S1
Bit 4
Bit 3
DI1
DI2
Dither amplitude according to parameterization
Status Byte S2
Bit 4
Bit 3
reserved
reserved
Dither amplitude according to parameterization
Version 1.3.0, valid from FW/HW-Version 01/01
WAGO-I/O-SYSTEM 750
Action
No change of value
Falling ramp
Rising ramp
No change of value
Bit 2
Bit 1
0
ON_
TARGET
Bit 2
Bit 1
reserved
ON_TARG
ET
Bit 0
READY
Bit 0
READY
Manual