106
Appendix
11.1.3.1.2 Acknowledgement
The following acknowledgements are defined:
Table 70: Acknowledgement
Value Explanation
0
INVALID
1
HOLD ACKNOWLEDGE Signal or confirmation that the channel is ready, but data is
2
RESET ACKNOWLEDGE Response to "RESET REQUEST" when Mailbox in reset.
3 ... 7 -
11.1.3.1.3 Signaling
In signal mode, the handshake byte appears as follows:
Table 71: Structure of the Handshake Byte
Bit 7
Bit 6
0
Table 72: Signaling
Value
0x00
0x32
0x33
(other)
Handshake byte
Bit 5
Bit 4
Bit 3
0
Signal
Explanation
INVALID SIGNAL
RESET SIGNAL
ERROR SIGNAL
-
750-632 Proportional Valve Module
Description
Signals that the receiver has not started operations again after
a reset.
not currently being transferred (e.g. because there is not any
data yet).
(not supported, ignore)
Bit 2
Bit 1
Bit 0
Description
State of the process image with no effect by Mailbox 2.0
Shows that the local Mailbox is in the process of
restarting
Shows that the local Mailbox is in the fault condition
Other values are not considered as signals and are
processed separately in the Status or Control nibble.