WAGO-I/O-SYSTEM 750
750-632 Proportional Valve Module
5.3.5

"STOP"

The "STOP" function can be achieved during operations automatically guided by
the I/O module by specifying "0" as the setpoint value. As a result, the I/O
module approaches this setpoint value at a speed according to the currently valid
ramp.
The "STOP" function can also be controlled via the digital inputs DI1 and DI2
using corresponding parameterization.

Figure 14: "STOP" Function via Digital Inputs

If "STOP" is triggered this way, then the autonomous "STOP" ramp is used. This
is not, however, the ramp that was already described, which is valid within the
context of the standard setpoint value control.
Manual
Version 1.3.0, valid from FW/HW-Version 01/01
Function Description
41